Supply air unit VEKC - Integrated Control Equipment Curo
26
FläktGroup DC_9965GB_20190124_R3
Specifications are subject to alteration without notice
7. PARAMETER LIST
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value Comments
Set Date and Time
R/W
–
–
–
Set Language
R/W
–
–
Swedish
Login
R/W
0000-9999
–
0000
For installers and Service personnel
Settings
For installers and Service personnel
1. Schedule
See section 4.7.
2. Commissioning Wizard
See section 4.6.
3. Timer Control
Timer control
R/W
1-6
–
1
See section 2.7
Timer Release Delay
R/W
0-9999
min
0
4. Fan Control
4.1 Fan settings
Boost Running Timer
R/W
Yes / No
–
No
Boost Running Time
R/W
0-9999
min
120
Startup Time
R/W
0-32767
s
15
Shut Down Time
R/W
0-32767
s
0
300 sec for unit with Electrical heater
Fireplace
R/W
0-360
min
30
Not för VEKA
4.2 COP / CAV
Not för VEKA
5. Heating / Cooling
5.1 Pre Heater
Not for VEKA
5.2 Heating/Cooling
Temperature control option
R/W
1-2
1
1 = Standard, supply air control. See section 5.2
2 =
Cascade control
See section 5.2
Minimum Supply temp
R/W
15-35
° C
15
Maximum Supply temp
R/W
15-35
° C
25
Cooling sequence
R/W
Yes/No
No
Cooling DX
R/W
Yes/No
No
Dead zone Cooling
R/W
Yes/No
Yes
Dead zone
R/W
0-25
° C
2
Block cooling in Winter
R/W
Yes/No
Yes
Block heating in Summer
R/W
Yes/No
Yes
Post Heater
R/W
Yes/No
Yes
Cascade reference
R/W
0-1
0
0 = Extract air control
1 =
Outdoor air compensation
Cascade A
R/W
–10-10
° C
0,5
Cascade B
R/W
–10-10
° C
–0,5
Relative / Absolute temperature
R/W
rel/abs
rel
Relative or absolute temperatures in Schedule
5.3 Night Cooling
Not for VEKA
5.4 Defrosting
Not for VEKA
5.5 Cooling Recovery
Not for VEKA
5.6 Summer / Winter mode
Current season mode
R
Summer / Winter
–
–
Automatic/Manual mode
R/W
Auto / Manuellt
–
Auto
Manual Summer / Winter mode
R/W
Summer / Winter
–
Winter
SETTINGS