HUMIDIFIER, FOR CIRCULATED WATER
Installation and maintenance instruction
11
FläktGroup
DC_8642GB 20180131_R0
Specifications are subject to alteration without notice
CONTROL EQUIPMENT
The control box is located on the exterior of the functional
section.
Internal components, such as the ultrasound sensor, solenoid
valve, actuator and circulation pumps 1 and 2 are wired to
the junction box.
ULTRASOUND SENSOR
The ultrasound sensor has an analogue output of 0–10 V, which
means that the water level can be read from the display to an
accuracy of a few millimetres.
MONITOR AND KEYPADS
MONITOR
The four-line display has 12 characters per line.
THE KEYPADS
The right arrow is used for navigation
between the 8 images on the screen that
show running information and other
settings. See below.
If the left arrow is held depressed,
this will force the drain pipe to open
(used for performance testing.)
All the arrow keys are used to move the
flashing cursor between the different
fields on the screen.
The plus and minus keys are used to:
- increase or decrease a flashing value
- choose between On and Off.
The Esc key is used to:
- advancing one step upward in the menu tree
- remove the flashing cursor
- reset an alarm or alarm output.
The OK key is used to:
- confirm a selection.
INFORMATION IMAGES
1. In-operation information in Swedish.
2. In-operation information in English.
3. In-operation information in German.
4. For setting water quality zone and time delay, T, for dilution.
5. For setting cleaning time for humidifier fills and tray.
(1–2 x 15 min./day)
6. For reading the factory preset values for each water level A,
B1, B2, B3 and C, sensor scaling factor F and pump function CP.
7. For setting time.
8. For setting inactive time.
IMAGE 1. IN-OPERATION INFORMATION IN SWEDISH
Line 1 shows: NOT RUNNING, RUNNING, HUMIDIFYING
Line 2 shows: DRAINING, DILUTION, FILLING, CLEANING
Line 3 shows: ALARM CP1-Q1, ALARM CP2-Q2, ALARM LEVEL
Line 4 shows: WATER 45 mm
IMAGE 2. IN-OPERATION INFORMATION IN ENGLISH
IMAGE 3. IN-OPERATION INFORMATION IN GERMAN
IMAGE 4. CHOOSING ZONE AND TIME DELAY
Do as follows to change zone.
Press arrow down until the figure 2 flashes. Use the + or – keys to
set the desired value, 1, 2 or 3. Press OK.
Selecting a lower value than 1 will still give zone 1.
Selecting a higher value than 3 will still give zone 3.
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
ESC
+
–
OK
- - - D R I F T - - - -
- Q 1
P Å F Y L L N I N G
A L A R M
C P 1
V A T T E N 4 5 m m
- - R
N
- - -
F I L L I N G U P
A L A R M
C P 1
W A T E R
4 5 m m
U N
F I L L I N G
I N G
U P
A L A R M
C P 1
W A T E R
4 5 m m
- Q 1
B E T R I E B - A N
N A C H F Ü L L U N G
A L A R M
C P 1
W A S S E R 4 5 m m
- Q 1
Z O N / Z O N E : 2
( 1 - 3 )
V E R Z Ö G E R U N G
D E L A Y
T = 2 0