eCO Premium™ - Installation & Maintenance
9
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
VALVE ACTUATOR FOR HEATING SV1 AND COOLING SV2
Connected to terminal in a connection box. Stroke length 5.5 mm.
Intended for assembly on 2-way and 3-way valves of the type
VVG44 or VXG44.
3-WAY VALVE
The bypass is closed by turning the spindle inwards, the bypass
is opened by turning the spindle outwards.
VALVES AND ACTUATORS
ACCEPTED INSTALLATION METHOD
VALVE FOR HEATING AND COOLING
The valve and valve actuator can be easily installed with out
special tools. A particle filter should be fitted before the valve to
extend its service life.
2-WAY VALVE
The flow is increased by turning the spindle inwards, the flow is
reduced by moving the spindle outwards. Note that the two-way
valve cannot be used as a three-way valve.
The flow direction in the valve is indicated by the arrow.
ACCEPTED INSTALLATION METHOD
ACCEPTED INSTALLATION METHOD
When installing a 3-port valve check as follows:
Mixture from A/B to AB
Distribution from AB to A/B