eCO Premium™ - Installation & Maintenance
26
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
TIMER FUNCTION 1
Timer 1
Timer 2
Manual/Automatic Mode
0
0
Trickle
1
0
Normal
0
1
Boost
1
1
TIMER FUNCTION 2
Timer 1
Timer 2
Manual/Automatic Mode
0
0
Trickle
1
0
Boost
0
1
Stop
1
1
TIMER FUNCTION 3
Timer 1
Timer 2
Manual/Automatic Mode
0
0
Normal
1
0
Boost
0
1
Stop
1
1
TIMER FUNCTION 4 (DEFAULT)
Timer 1
Timer 2
Stop
0
0
Manual/Automatic Mode
1
0
Stop
0
1
Boost
1
1
TIMER FUNCTION 5
Timer 1
Timer 2
Stop
0
0
Manual/Automatic Mode
1
0
Stop
0
1
Normal
1
1
SCHEDULES (CONT) & TIMER FUNCTION
A single date schedule can be cancelled by setting the schedule
date to any date earlier than the current date.
A single date period schedule can be cancelled by setting both
the From and To schedule dates to any date earlier than the cur-
rent date.
DATE PERIOD SCHEDULE
A date period schedule is defined as a one-off schedule that is
configured to run between any to dates, staring at 00:00:00 on
the first date and finishing at 23:59:59 on a second date.
During a weekly schedule, the fans can be set to run at any of the
available speeds: Stop, trickle, normal or Boost.
The four individual date period schedules are prioritized to
remove the potential for time periods to clash with each other.
Date Period 4 Schedule has the highest priority and Date Period 1
Schedule the lowest priority. If two or more date period schedules
have start and end times that clash with each other, only the
schedule with the highest priority will be used, the other(s) will be
ignored.
The supply and extract fans will run at the same speed when
setup through a date period schedule.
SINGLE DATE SCHEDULE
A single date schedule is defined as a one-off schedule that
automati cally starts and finishes on the same date and runs for
the whole day, i e, from 00:00:00 to 23:59:59.
During a single date schedule, the fans can be set to run at any
of the available speeds: Stop, trickle, normal or Boost.
The four individual single date schedules are prioritized to remove
the potential for time periods to clash with each other. Single
Date 4 Schedule has the highest priority and Single Date 1 Sched-
ule the lowest priority. If two or more single date schedules have
start and end times that clash with each other, only the schedule
with the highest priority will be used, the other(s) will be ignored.
The supply and extract fans will run at the same speed when set-
up through a single date schedule.
TIMER CONTROL
The Timer Control setting determines what speed the fans will
run at when up to two external, volt-free switches are applied to
the TM1 and PIR terminals - refer to page 12 for customer wiring
options.
A ’0’ in the tables below indicates a volt-free open-circuit input
and ’1’ indicates a volt-free short-circuit input.