Maintenance
CAIR
fricostar
®
70
FläktGroup DC-2009-0019-GB 2018-01/R9 • Specifications are subject to alteration without notice
9.10 Liquid-coupled energy recovery coil
Refer to „Heater assembly (pumped warm water)“ on page 68.
9.11 Plate-type heat exchanger
A plate-type heat exchanger operates without any external, mechanical or electrical
actuators, is not equiped with any moving components and its service life can be neg-
atively influenced only by corrosion.
Carry out the following maintenance steps:
•
Carry out cleaning depending on contamination degree of the plate assembly.Use a
hair broom to remove dry dust and fibres at the coil inlet, blow out.
•
Check bypass damper for proper operation, if required.
•
Complete wet cleaning only if a tray is installed and available!
Oil and grease
•
Remove oil and grease deposits with hot water and grease-dissolving cleaning
agents.
9.12 Damper blades and shut-off dampers
Carry out the following maintenance steps:
•
Vacuum clean dampers (blow out),
never apply grease!
•
Detach the actuator from dampers, check if dampers are moving freely.
•
Check that the damper actuator moves to its final positions.
9.13 Sound attenuator
Carry out the following maintenance steps:
•
Check the sound attenuator section and sound insulating splitters for contamination,
vacuum clean, if necessary.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS!
Please consider the safety instructions on page 58.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS! OB-
SERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 58.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS! OB-
SERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 58.