Maintenance
CAIR
fricostar
®
68
FläktGroup DC-2009-0019-GB 2018-01/R9 • Specifications are subject to alteration without notice
Replacing filter medium
•
Ensure that unit is deactivated. Open the access door/maintenance panel.
•
Release the top and bottom springs clips on the filter rack or open the quick-release
filter frame.
•
Pull out the filter frame.
•
Replace a damaged or dirty filter.
•
Slide the filter frame into the unit. Ensure an airtight seal and proper fit!
•
Close the top and bottom spring clips on the filter rack or close the quick-release
filter frame.
•
Install filter bags only in the upright position!
•
Close the service access door or maintenance panel.
9.5.3 HEPA filters
Refer to the relevant maintenance instructions specified in the supplied documenta-
tion.
9.5.4 Maintenance of other filters
Refer to the relevant maintenance instructions specified in the supplied documenta-
tion.
9.6
Heater assembly
9.6.1 Heater assembly (pumped warm water)
Carry out the following maintenance steps:
•
Check for leak-free condition and possible dirt on the air side.
•
To ensure frost protection, periodically check the safety devices and take proper
precautions such as draining the equipment or adding antifreeze agents.
•
Ensure that pipework connections and mountings are securely fixed.
•
If necessary, clean the coil on the air side (blow out with compressed air or low-
pressure water).
•
Air vent.
9.6.2 Electric heater assembly
•
Carry out dry cleaning on the air side.
9.7
Cooler assembly
ELECTRICAL HAZARD AND DANGER OF ROTATING UNIT PARTS WITH
SHARP EDGES! OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 58 and page 60.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS!
Please consider the safety instructions on page 58.
ELECTRICAL HAZARD AND DANGER OF ROTATING UNIT PARTS WITH
SHARP EDGES! OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 58 and page 60.