Fläkt Woods
8217 GB 2014.07.02 7
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Valve actuator for heating SV1 and
cooling SV2
Connected to terminal in electrical cabinet. Stroke length
5.5 mm. Intended for assembly on 2-way and 3-way
valves of the type VVG44 or VXG44.
3-way valve VXG
The bypass is closed by turning the spindle inwards, the
bypass is opened by turning the spindle outwards.
Sensors and accessories
Accepted installation method
Valve for heating and cooling
The valve and valve actuator can be easily installed with-
out special tools. A particle filter should be fitted before
the valve to extend its service life.
2-way valve VVG
The flow is increased by turning the spindle inwards, the
flow is reduced by moving the spindle outwards.
Note that the two-way valve cannot be used as a three-
way valve.
The flow direction in the valve is indicated by the arrow.
Accepted installation method
Accepted installation method
When installing a 3-port valve check as follows:
Mixture from A/B to AB
Distribution from AB to A/B