- 8 -

 

-10º C / 8º F. 

 
11. Heat Exchanger should be cleaned if smokey conditions continue even after 

the air adjustments on the burner are made. 

 

 

START UP INSTRUCTIONS: 

 

 

1. 

Position heater properly on a level surface. 
 

2. 

Be sure the toggle switch in is the “OFF” position. 

 

3. 

Ensure burner “air gate” is properly set at 3. 

 

4. 

Ensure electrical cord is grounded and plugged into a 120V 15AMP 
outlet. Verify cord size (12/3AWG at 50ft & 10/3AWG at 100ft) 

 

5. 

The power indicator light on the control box will engage. If the green 
light illuminates, you have proper power supply. If not, refer to sticker 
on heater to verify warning problem. Correct power supply problem 
before operating heater. 

 

6. 

Move toggle switch to “MANUAL” position for manual control. 

 

7. 

Move toggle switch to “THERMOSTAT” position for thermostat  control. 
Thermostat must be plugged into heater first. 

 
 
Please Note: 

 
1.  If using Thermostat on unit, unit must be started in Thermostat position. 
 
2  When  changing  between  manual  and  thermostat  operation,  the  heater 

must  be  left  in  the  “OFF”  position  for  30  seconds  to  prevent  the  burner 
from locking out. 

 
3.  When using a generator for electrical supply, make sure the generator 

is properly grounded and generator is at a 60Hz frequency. 
 

4.  In the event that a Generator is being used and the generator runs out of 

fuel, make sure the heater switch is in the “OFF” position before restarting 
generator, failure to do so may damage heater. 

 
 

 
 

Summary of Contents for FVO-200RC

Page 1: ...T FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U S A As per CSA B140 8 Portable Oil Fired Heaters CSA B140 02003 Oil Burning Equipment UL733 Oil fired heaters Construction Heaters Unattended Ty...

Page 2: ...ON SUCH AS AN INSTRUCTIONS MANUAL LABELS ETC CONTACT THE MANUFACTURER WARNING FIRE BURN INHALATION AND EXPLOSION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DIS...

Page 3: ...HORITY IF YOU HAVE QUESTIONS ABOUT APPLICATIONS Other standards govern the use of fuel gases and heat producing products in specific applications Your local authority can advise you about these SPECIF...

Page 4: ...This heater will operate with No 1 No 2 Diesel or Kerosene Note No 1 Fuel Oil or Kerosene must be used for temperatures less than 10 C 8 F ELECTRICAL WARNING Electrical Grounding Instructions This app...

Page 5: ...PPLY BEFORE TURNING HEATER ON FAILURE TO DO SO WILL VOID ANY WARRANTY FLUE PIPE Flue pipe connection must terminate with a vertical run at least 2ft long Horizontal runs should have a rise ratio of 1...

Page 6: ...MINIMUM OF 2FT HIGHER THAN ANY POINT WITHIN 10FT B MAXIMUM HORIZONTAL RUN IS 30FT NOTE 90deg ELBOW 10ft HORIZONTAL VENT ALLOWANCE 45deg ELBOW 5ft HORIZONTAL VENT ALLOWANCE C VENT TERMINATION IN HORIZO...

Page 7: ...hose is cut it must be replaced prior to the heater being put into operation The replacement hose assembly shall be that specified by the manufacturer 3 The flow of combustion and ventilation air must...

Page 8: ...oblem Correct power supply problem before operating heater 6 Move toggle switch to MANUAL position for manual control 7 Move toggle switch to THERMOSTAT position for thermostat control Thermostat must...

Page 9: ...heater to start properly 3 Make sure there are no air locks in fuel lines or filter 4 Ensure proper power supply and extension cord is being used 5 Check for dirty fuel filter or blocked fuel supply...

Page 10: ...y guards or performing any maintenance be sure that the main power supply is disconnected COMBUSTION AIR ADJUSTMENTS NOTE Proper combustion air adjustment must be achieved using a certified combustion...

Page 11: ...O2 and temperature readings may be experienced when the burner cover is put in place Therefore the burner cover must be in place when making the final combustion instrument readings to ensure proper t...

Page 12: ...r application Turn the temperature feeler gauge so that the holes are parallel with the heat exchanger This will help the fan switch to remain cool and not overheat See following If supply air is cold...

Page 13: ...13 WARNING DO NOT activate burner until proper oil line connections have been made or failure of the pump shaft seal may occur...

Page 14: ...14 WARNING If a neutral or ground lead is attached to this terminal the CONTROL BOX on the burner will be damaged should lockout occur...

Page 15: ...fully pulling it back and then up B Remove the AIR TUBE COVER PLATE 5 by loosening the two retaining SCREWS 4 C Loosen SCREW 2 and then slide the complete drawer assembly out of the combustion head as...

Page 16: ...2 from the DRAWER ASSEMBLY by loosening the SCREW 1 B Insert the proper NOZZLE into the NOZZLE ADAPTER and tighten securely Do not over tighten C Replace adapter with nozzle installed into drawer ass...

Page 17: ...ressure gauge is attached to the PRESSURE PORT 8 for pressure readings Two PIPE CONNECTORS 5 are supplied with the burner for connection to either a single or a two pipe system Also supplied are two A...

Page 18: ...OSTAT FAN MOTOR FV 200 WIRING SCHEMATIC FV 200 WS 2011 FV 200 SERIES WIRING SCHEMATIC 2011 FLAGRO INDUSTRIES LIMITED SWITCH BURNER REAR HIGH LIMIT SWITCH FRONT HIGH LIMIT SWITCH L1 N G G X RED LIGHT P...

Page 19: ...2P05RC Motor Mount Bracket FV 208RC Recirculating Hood FV 208IFP Canopy Inner Faceplate FV 208IR Canopy inlet Ring FV 2P08RC Control Box FV 2P09RC Control Box Lid FV 406 High Limit Switch Outet 250F...

Page 20: ...FV 461 Inlet Outlet Burner Pump Fitting FVO 223 7 Copper Pick Up Tube c w Adapter FV 231 Burner Gasket FV 433 Feeler Gauge FV 234CB12 Front Face Plate 1 x 12 FV 234CB16 Front Face Plate 1 x 16 FV 235...

Page 21: ...1 2 4 18 19 20 21 22 A B B B 23 24 25 26 28 30 31 32 33 34 35 36 38 39 37 40 40 27 27 F 5 OIL FIRED BURNER PARTS DIAGRAM...

Page 22: ...034 BURNER MOTOR 25 FVO 3007316 AIR TUBE COVER PLATE 26 FVO 3002280 PHOTO CELL 27 FVO 3005854 SEMI FLANGE 28 FVO 3005855 MOUNTING FLANGE 30 FV 3005708 BURNER FAN 31 FVO 3005844 BURNER CAPACITOR 32 FVO...

Reviews: