- 8 -
-10º C / 8º F.
11. Heat Exchanger should be cleaned if smokey conditions continue even after
the air adjustments on the burner are made.
START UP INSTRUCTIONS:
1.
Position heater properly on a level surface.
2.
Be sure the toggle switch in is the “OFF” position.
3.
Ensure burner “air gate” is properly set at 3.
4.
Ensure electrical cord is grounded and plugged into a 120V 15AMP
outlet. Verify cord size (12/3AWG at 50ft & 10/3AWG at 100ft)
5.
The power indicator light on the control box will engage. If the green
light illuminates, you have proper power supply. If not, refer to sticker
on heater to verify warning problem. Correct power supply problem
before operating heater.
6.
Move toggle switch to “MANUAL” position for manual control.
7.
Move toggle switch to “THERMOSTAT” position for thermostat control.
Thermostat must be plugged into heater first.
Please Note:
1. If using Thermostat on unit, unit must be started in Thermostat position.
2 When changing between manual and thermostat operation, the heater
must be left in the “OFF” position for 30 seconds to prevent the burner
from locking out.
3. When using a generator for electrical supply, make sure the generator
is properly grounded and generator is at a 60Hz frequency.
4. In the event that a Generator is being used and the generator runs out of
fuel, make sure the heater switch is in the “OFF” position before restarting
generator, failure to do so may damage heater.