background image

 

 

damage the media filter or cause mineral deposits to 
build up on the filter. 

AIR CONDITIONING 

Whenever possible, your Air Cleaner should be installed 
upstream of the cooling coil. This will clean the air before 
it reaches the evaporator coil. 

 
GENERAL INSTALLATION STEPS 

1. 

Remove existing equipment filter and clean 
blower compartment:

  Thoroughly clean the blower 

compartment, since your Air Cleaner cannot remove 
dirt from the blower chamber and distribution ducts. 

2. 

Leave sufficient room around your Air Cleaner:

 

There must be adequate room to remove the filter. 
Additional room must be left above the Air Cleaner, 
if it is to be upgraded to a High Efficiency Electronic 
Air Cleaner. 

 

NOTE:

  Once your Air Cleaner has been installed, 

do not allow the placement of a new hot water 
heater, water softener, gas pipe, or electrical cable 
to be put in front of or within 12 in (30 cm) from the 
top of the Air Cleaner. Otherwise, this will not allow 
for the removal of the Air Cleaner filters, which are 
necessary for maintenance or upgrading later. 

3. 

Installing the cabinet:

  Make sure rivets or screws 

do not protrude into the cabinet, causing filters to 
catch. 

4. 

Transitions:

  When the air duct does not fit the Air 

Cleaner opening, a gradual transition is 
recommended to reduce air turbulence through the 
Air Cleaner and to increase its efficiency. There 
should not be more than 20

o

  of expansion used on 

each side of the transition fitting, approximately 4 
inches per running foot (10 cm per 30 cm).   
 

Do not reduce ductwork to fit a smaller Air 
Cleaner.  This will increase the velocity of air 
flow and may decrease cleaning efficiency. 

5. 

Turning vanes:

  If the Air Cleaner is installed 

adjacent to an elbow or angle fitting, turning vanes 
are recommended to improve air distribution across 
the filter. 

6. 

Seal the joints in the return air system:

  All joints 

between the Air Cleaner and the heating/cooling 
equipment should be sealed to prevent dust from 
entering the clean air stream. 

 
To improve the performance of your Air Cleaner, 

these simple steps should be followed: 

 

Run your heating/cooling system fan continuously, 
on low speed if available, since your Air Cleaner 
only removes particulate matter which passes 
through to the filter. 

 

Remove furniture or carpets from the front of the 
return air grilles so that air moves freely to the 
heating/cooling equipment. 

 

Check the fan belt on the furnace blower and see 
that there is no more than approximately 1/2 in (1.3 
cm) of play on each side. A loose belt slips on the 
pulley. 
 

MAINTENANCE

 

CAUTION 

Turn off your heating/air conditioning system fan 
before performing maintenance to your Air Cleaner. 

The media filter needs  to be replaced once or twice a 
year depending on the amount of contaminants in the 
air. If the filter is allowed to become too clogged, it may 
cause a restriction to the air flow through the system. 
This may cause poor circulation of conditioned air or the 
evaporator coil of the air conditioning system to freeze 
up. 

 
1.  Remove Air Cleaner door. 
2.  Remove filters and discard.  
3.  Install new filter. Arrow must point toward the system 

fan. 

4.  Close Air Cleaner door. 

 

 
 
Replacement Media Filters 
Part #M1-1056   

 

Requires (2) 

 
When replacement filters are required, contact your 
original installer or dealer. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for FSMF3225

Page 1: ...aner is ideal for 5 ton air handling systems Handles up to 2800 cfm High Efficiency MERV 11 Media Filters 2 remove airborne pollutants as small as 0 3 micron No maintenance except for filter replacement No electrical hook up required Heavy gauge galvanized steel cabinet and powder coat paint finish resist corrosion and provide trouble free installation ...

Page 2: ...r ducts of the heating cooling system to the Media Air Cleaner Here the particles are captured by the media filter The media filter is constructed of continuous hydrophobic polyolefin fibres that will not shred or absorb moisture The media s unique design features a structured density gradiant with an electret charge for higher initial and sustained efficiency The media is supported by an open ste...

Page 3: ...ller Air Cleaner This will increase the velocity of air flow and may decrease cleaning efficiency 5 Turning vanes If the Air Cleaner is installed adjacent to an elbow or angle fitting turning vanes are recommended to improve air distribution across the filter 6 Seal the joints in the return air system All joints between the Air Cleaner and the heating cooling equipment should be sealed to prevent ...

Page 4: ...g of either defective parts or replacement parts Such costs may be covered by a separate warranty provided by the FIVE SEASONS dealer LIMITATIONS OF WARRANTY All implied warranties including implied warranties of merchantability are hereby limited in duration to the period for which the limited warranty is given The expressed warranties made in this warranty are exclusive and may not be altered en...

Reviews: