Instruction Manual
D103622X0KR
TopWorx 4310
October 2016
4
D
For instruments with a hollow liquid level displacer, the displacer might retain process fluid or pressure. Personal injury
or property damage due to sudden release of pressure, contact with hazardous fluid, fire, or explosion can be caused by
puncturing, heating, or repairing a displacer that is retaining process pressure or fluid. This danger may not be readily
apparent when disassembling the sensor or removing the displacer. Before disassembling the sensor or removing the
displacer, observe the appropriate warnings provided in the sensor instruction manual.
D
Personal injury or property damage, caused by fire or explosion from the leakage of flammable or hazardous gas, can
result if a suitable conduit seal is not installed. For explosion‐proof applications, install the seal no more than 457 mm
(18 inches) from the instrument when required by the nameplate. For ATEX applications use the proper cable gland
certified to the required category. Equipement must be installed per local and national electric codes.
D
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D
If installing into an existing application, also refer to the WARNING in the Maintenance section.
Special Instructions for Safe Use and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation requirements
and/or conditions of safe use. Special instructions are listed by agency/approval. To get these instructions, contact
Emerson Process Management sales office
. Read and understand these special conditions of use before installing.
WARNING
Failure to follow conditions of safe use could result in personal injury or property damage from fire or explosion, or area
re‐classification.
Operation
With instruments, switches, and other accessories that are controlling valves or other final control elements, it is
possible to lose control of the final control element when you adjust or calibrate the instrument. If it is necessary to
take the instrument out of service for calibration or other adjustments, observe the following warning before
proceeding.
WARNING
Avoid personal injury or equipment damage from uncontrolled process. Provide some temporary means of control for the
process before taking the instrument out of service.
Maintenance
WARNING
Before performing any maintenance operations on an actuator‐mounted instrument or accessory: