Instruction Manual
D104296X012
LCP200 Local Control Panel
August 2018
3
Table 1. Specifications
Power Options
J
External: 12VDC to 26.4VDC @ 50 mA maximum
continuous current (100 mA maximum inrush)
J
Loop: 8-20 mA (LCP200 and DVC6200 SIS
combined)
Continuous Power Consumption
External:
1.4 W max
Loop (Point-to-Point):
48 mW
Loop (Multi-Drop):
120 mW
Temperature Limits
-40 to 65
_
C (-40 to 149
_
F)
Maximum distance between LCP200 and
DVC6200 SIS digital valve controller
Cable length is limited by maximum cable
capacitance of 340,000 pF
. Typical 1000 meters
(3280 feet) with 18 AWG shielded Audio, Control
and Instrumentation Cable
Contact Type and Ratings
Three single-pole double-throw (SPDT) relay switches
Each output is capable of 30 VDC with maximum
current of 200 mA at room temperature
Contact Operation
Reset:
Activated for 1.5 to 3 seconds when Reset
button is pressed for 0.5 seconds or more
Trip:
Activated for 1.5 to 3 seconds when Trip button
is pressed for 0.5 seconds or more
Test:
Activated when partial stroke test is in progress
Electrical Classification
Pollution Degree IV, Overvoltage Category II per IEC
61010 clause 5.4.2d
Electrical Housing
IP66, Type 4X
Hazardous Area
FM (United States and Canada)
—Intrinsically Safe for
Gas and Dust
ATEX
—Intrinsically Safe for Gas and Dust
IECEx
—Intrinsically Safe for Gas and Dust
Electromagnetic Interference (EMI)
Meets EN 61326-1:2013
Immunity—Industrial locations per Table 2 of
EN 61326-1 Standard. Performance is
shown in table 2 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Connections
Two Conduit entries:
J
3/4 NPT or
J
M20
Wiring
14 to 26 AWG
Electrical Installation
Wire connections are polarity sensitive
Compatibility
DVC6200 SIS with Firmware revision 3 or later
DVC6000 SIS with Firmware revision 7 or later
Installation Orientation
Conduit entry locations must be facing down
Dimensions
406 mm long by 165 mm wide by 105 mm deep
See figure 2
Adapter is available for replacing the LCP100
Construction Materials
Housing material:
316SST
Approximate Weight
16.8 kg (37 lbs)
Lights
Top (Green/Normal):
Solid when the valve is at its
normal operating position, and loop current is normal
Middle (Red/Trip):
Solid when the valve is at its trip
position and middle (Trip) loop current is tripped
Bottom (Yellow/Ready-to-Reset):
Solid when the
valve is latched in the trip position, and loop current is
normal
-continued-