Troubleshooting
148
Electrical Control System
2.4.4.11. J1 malfunction
When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52°C.
P5 display
High
temperature
protection
of
condenser
Check whether the
condenser temperature is
Higher than 65°C
Yes
Check whether the
resistance of condenser
temp. sensor is normal
refer
to
the
Appendix
1
Replace
the
temperature
sensor
No
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop
the
unit
Yes
Check
if
the
outdoor
unit
ventilation
is
good
Yes
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Replace outdoor main
board
No
Refrigerant
is
not
enough
add
the
refrigerant
No
Check
if
the
outdoor
fan
runs
properly
please
refer
to
the
solution
of
fan
speed
has
been
out
of
control
malfunction
.
Find
out
the
cause
and
have
it
solved.
No
Yes
No
Correct
the
connection
No
Yes
Check
the
connection
between
temperature
sensor
and
PCB.
Yes
J1
Summary of Contents for FSFIF-121AE2
Page 12: ...Service Space 10 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 14: ...Air Velocity Distributions Reference Data 12 Indoor Units 30 36K Cooling Heating ...
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 48 60K Cooling Heating ...
Page 20: ...Field Wiring 18 Indoor Units 9 Field Wiring ...
Page 28: ...Static Pressure 26 Indoor Units 4 Static Pressure FSLIF 182AE2 FSLIF 242AE2 ...
Page 29: ...Static Pressure Indoor Units 27 FSLIF 301AE2 FSLIF 362AE2 ...
Page 30: ...Static Pressure 28 Indoor Units FSLIF 481AE0 FSLIF 602AE0 ...
Page 35: ...Field Wiring Indoor Units 33 9 Field Wiring ...
Page 37: ...Wiring Diagram Indoor Units 35 FSLIF 362AE2 ...
Page 38: ...Wiring Diagram 36 Indoor Units ...
Page 42: ...Service Space 40 Indoor Units 3 Service Space ...
Page 51: ...Wiring Diagram Indoor Units 49 Field Wiring 9 ...
Page 52: ...Wiring Diagram 50 Indoor Units 10 Wiring diagram FSPIF 181AE2 ...
Page 53: ...Ceiling Floor Type Indoor Units 51 FSPIF 241AE2 FSPIF 301AE2 ...
Page 54: ...Wiring Diagram 52 Indoor Units FSPIF 362AE2 FSPIF 480AE0 FSPIF 601AE0 ...
Page 58: ...Service Space 56 Indoor Units 3 Service Space ...
Page 62: ...60 Indoor Units 9 Field Wiring FSKIF 121AE2 EU FSKIF 184AE2 EU 12k unit Field Wiring ...
Page 63: ...Indoor Units 61 10 Wiring diagram FSKIF 121AE2 EU FSKIF 184AE2 EU Wiring Diagram ...
Page 67: ...Console Type 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 Indoor Units 63 ...
Page 68: ...Console Type 3 Service Space 64 Indoor Units ...
Page 73: ...Console Type 9 Field Wiring Indoor Units 69 FSFIF 121AE2 12 ...
Page 74: ...Console Type 10 Wiring diagram 70 Indoor Units FSFIF 121AE2 ...
Page 76: ...Outdoor Units 72 Outdoor Units ...
Page 78: ...Dimensions 74 Outdoor Units Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 84: ...Wiring diagram 80 Outdoor Units 7 Wiring diagram FSOIF 121AE2 FSOIF 183AE2 ...
Page 85: ...Wiring diagram Outdoor Units 81 FSOIF 301AE2 FSOIF 243AE2 FSOIF 362AE2 3F ...
Page 86: ...Wiring diagram 82 Outdoor Units FSOIF 482AE0 3F FSOIF 602AE0 3F ...
Page 87: ...Wiring diagram Outdoor Units 83 ...
Page 105: ...Installation 101 ...
Page 110: ...Refrigerant pipe installation 106 Installation ...
Page 145: ...Troubleshooting Electrical Control System 141 2 4 4 3 J4 malfunction J4 ...
Page 154: ...Troubleshooting 150 Electrical Control System 2 4 4 13 J0 malfunction J0 ...