Drainage pipe installation
110
Installation
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note:
Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
Summary of Contents for FSFIF-121AE2
Page 12: ...Service Space 10 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 14: ...Air Velocity Distributions Reference Data 12 Indoor Units 30 36K Cooling Heating ...
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 48 60K Cooling Heating ...
Page 20: ...Field Wiring 18 Indoor Units 9 Field Wiring ...
Page 28: ...Static Pressure 26 Indoor Units 4 Static Pressure FSLIF 182AE2 FSLIF 242AE2 ...
Page 29: ...Static Pressure Indoor Units 27 FSLIF 301AE2 FSLIF 362AE2 ...
Page 30: ...Static Pressure 28 Indoor Units FSLIF 481AE0 FSLIF 602AE0 ...
Page 35: ...Field Wiring Indoor Units 33 9 Field Wiring ...
Page 37: ...Wiring Diagram Indoor Units 35 FSLIF 362AE2 ...
Page 38: ...Wiring Diagram 36 Indoor Units ...
Page 42: ...Service Space 40 Indoor Units 3 Service Space ...
Page 51: ...Wiring Diagram Indoor Units 49 Field Wiring 9 ...
Page 52: ...Wiring Diagram 50 Indoor Units 10 Wiring diagram FSPIF 181AE2 ...
Page 53: ...Ceiling Floor Type Indoor Units 51 FSPIF 241AE2 FSPIF 301AE2 ...
Page 54: ...Wiring Diagram 52 Indoor Units FSPIF 362AE2 FSPIF 480AE0 FSPIF 601AE0 ...
Page 58: ...Service Space 56 Indoor Units 3 Service Space ...
Page 62: ...60 Indoor Units 9 Field Wiring FSKIF 121AE2 EU FSKIF 184AE2 EU 12k unit Field Wiring ...
Page 63: ...Indoor Units 61 10 Wiring diagram FSKIF 121AE2 EU FSKIF 184AE2 EU Wiring Diagram ...
Page 67: ...Console Type 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 Indoor Units 63 ...
Page 68: ...Console Type 3 Service Space 64 Indoor Units ...
Page 73: ...Console Type 9 Field Wiring Indoor Units 69 FSFIF 121AE2 12 ...
Page 74: ...Console Type 10 Wiring diagram 70 Indoor Units FSFIF 121AE2 ...
Page 76: ...Outdoor Units 72 Outdoor Units ...
Page 78: ...Dimensions 74 Outdoor Units Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 84: ...Wiring diagram 80 Outdoor Units 7 Wiring diagram FSOIF 121AE2 FSOIF 183AE2 ...
Page 85: ...Wiring diagram Outdoor Units 81 FSOIF 301AE2 FSOIF 243AE2 FSOIF 362AE2 3F ...
Page 86: ...Wiring diagram 82 Outdoor Units FSOIF 482AE0 3F FSOIF 602AE0 3F ...
Page 87: ...Wiring diagram Outdoor Units 83 ...
Page 105: ...Installation 101 ...
Page 110: ...Refrigerant pipe installation 106 Installation ...
Page 145: ...Troubleshooting Electrical Control System 141 2 4 4 3 J4 malfunction J4 ...
Page 154: ...Troubleshooting 150 Electrical Control System 2 4 4 13 J0 malfunction J0 ...