7.12.3 Heating:
The set temperature decrease 1°C per hour. Two hours later, the set temperature will maintain as a constant and the air
circulation is kept at low speed (Anti-cold function takes precedence over all).
Time
Room temperature
2
1
1'C
1'C
7.12.4 Auto:
After an hour running under economic mode, the set temp will rise 1°C, if it is under cooling mode; the set temp will
decrease 1°C,if it is under heating mode; the set temp will be changeless, if it is under fan-only mode; the condition will be
the same after the air conditioner running under economic mode after 2 hours, and during the next time the set temp do not
change. The total time is 7 hours, after 7 hours the unit stops.
7.13 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure
when power returns.
7.14 Ionizer
+
(air clean) function
7.14.1 Ionizer
+
(air clean) function is effected when the unit is working and controlled by the remote controller.
7.14.2 This function is active when the unit received the signal from the remote controller first time and inactive when
received the signal again. Repeat this circle when received signal again.
7.14.3 This function is working only when the indoor fan is working.
7.14.3 This function will not stop when the working mode changed, and be inactive when the unit shut down.
29