7.4 Operation Modes and Functions
7.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
a
b
c
d
T 1
e
7.4.2 Cooling Mode
7.4.2.1 Compressor running rules
When T1-Ts<-2
℃
, the compressor will stop,
when T1
—
T
S
>-0.5
℃,
the compressor will be activated.
When the AC run in mute mode, the compressor will run with low frequency.
When the current is more than setting value, the current protection function will be activated, and the
compressor will stop.
7.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different
T 4
A +
A
B
C
D
E
Summary of Contents for FSAI-SU-120AE2
Page 12: ...12 4 2 Wiring Diagram Indoor unit FSAI SU 90AE2 FSAI SU 120AE2 Outdoor unit FSOAI SU 90AE2 ...
Page 13: ...13 Outdoor unit FSOAI SU 120AE2 ...
Page 45: ...45 8 2 6 Refrigerant Leakage Detection diagnosis and solution EC ...
Page 46: ...46 8 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 47: ...47 8 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 48: ...48 8 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 49: ...49 8 2 10 Inverter compressor drive error diagnosis and solution P4 ...