5.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Summary of Contents for FSAI-SU-120AE2
Page 12: ...12 4 2 Wiring Diagram Indoor unit FSAI SU 90AE2 FSAI SU 120AE2 Outdoor unit FSOAI SU 90AE2 ...
Page 13: ...13 Outdoor unit FSOAI SU 120AE2 ...
Page 45: ...45 8 2 6 Refrigerant Leakage Detection diagnosis and solution EC ...
Page 46: ...46 8 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 47: ...47 8 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 48: ...48 8 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 49: ...49 8 2 10 Inverter compressor drive error diagnosis and solution P4 ...