Meanwhile, the maximum frequency is limited by the indoor fan speed.
Indoor fan speed
Maximum frequency
High speed/8 degree heating/ turbo function
No limit
Medium speed
FHeatMaxMidFan
Low speed/sleep mode
FHeatMaxLowFan
Silent mode
Fixed at F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While the zones of A,B,C... are corresponding to different compressor running frequency.
Temperature compensation: ΔT=4°C as default (it can be modified by the service).
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A: Increase the frequency to 3 grade higher until to FREMAX.
B~E: Increase the frequency to 2 grade higher until to FREMAX.
F~G: Increase the frequency to 1 grade higher until to FREMAX.
H: Keep the current frequency.
I: Decrease the frequency to the 1 grade lower until to F1.
J: Run at F1 for 1h. (if T1-Ts-ΔT >2
℃
, the compressor will stop)
Summary of Contents for FSAI-Pro-122AE2
Page 11: ...11 5 Wiring Diagram 5 1 Indoor Unit FSOAI Pro 92AE2 FSAI Pro 122AE2 ...
Page 12: ...12 5 2 Outdoor Unit FSOAI Pro 92AE2 ...
Page 13: ...13 FSOAI Pro 122AE2 ...
Page 55: ...55 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 56: ...56 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 57: ...57 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 58: ...58 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...