8.4.3 Heating Mode
8.4.3.1 Compressor running rules
The maximum operation frequency of the compressor after starting submits to the following rule.
Fmax=T4FREHEATMAX1
34
T4
Off
33
28
27
25
24
22
21
19
18
16
17
15
14
12
11
6
5
Fmax=T4FREHEATMAX2
Fmax=T4FREHEATMAX3
Fmax=T4FREHEATMAX4
Fmax=T4FREHEATMAX5
Fmax=T4FREHEATMAX6
Fmax=T4FREHEATMAX7
Fmax=T4FREHEATMAX8
1
0
-3
-4
-7
-8
-11
-12
-15
-16
Fmax=T4FREHEATMAX9
Fmax=F21
Fmax=F22
Fmax=F23
Fmax=F24
Fmax=F25