CLEARANCES — CGI905D MODELS
CLEARANCE DIMENSIONS
CGI905D
MM
A
Minimum clearance from top of trivets to:
z
Rangehood
650
z
Overhead exhaust fan
800
z
Downward facing combustible surface*
650
z
Downwards-facing tiled or fire resistant surface
500
B
Minimum clearance below bench top to:
z
Combustible surface
70
z
Fisher & Paykel oven or nearest non-combustible surface
65
C
Minimum clearance from side of cutout to nearest adjacent combustible surface
115
D
Minimum distance from right edge of cooktop to gas connection point on wall
(if using a flexible hose)
250
E
Distance from floor to gas connection point on wall
(if using a flexible hose)
800-850
F
Minimum clearance from countertop to overhead cabinet
(not directly above the cooktop)
450
G
Maximum depth of overhead cabinetry
600
H
Minimum distance between overhead cabinets
(centered above cooktop)
900
I
Minimum clearance from rear edge of cutout to nearest:
z
Combustible surface
85
z
Non-combustible surface
45
A
H
f
f
b
C
C
D
E
g
i
*Combustible surface definition
Any materials of a building structure or decorative structure made of wood, compressed paper,
plant fibres, vinyl/plastic or other materials that are capable of transferring heat or being
ignited and burned. Such material shall be considered combustible even though flame-proofed,
fire-retardant treated or surface-painted, or plastered.
Ensure there is an earthed power outlet within 900mm of the centre rear of the product. The gas
connector on the wall should be accessible with the product installed.
11