Standards Requirements

Australian and New Zealand Gas Installation 
Standards (AS5601, NZS 5261) require a 
cooktop to be installed so that the surface 
temperature of any nearby combustible 
surface will not exceed 65

o

C above ambient. 

Typically this is achieved by:

A

 

Having the cooktop spaced away from 
the wall (see “Clearances” for dimensions) 
[Dimension 

c

 and 

d

]

OR

B

  by protecting the wall, to at least 150 mm 

high [Dimension 

g

] along it’s length, with 

non-combustible surface materials, such as:
- 5 mm thick ceramic tiles alone are 

adequate.

- Tempered glass or sheetmetal (min. 0.4 mm 

thick) is acceptable when used in front of a 
fire resistant material.

- Fisher & Paykel Splashback (not available 

in Australia): This is stainless steel with a 10 
mm air gap to the wall.  When used with 
a 10 mm gap behind the product to the 
front of the splashback.  (Only with SB90 
series and SB1216 splashbacks.)

These products meet the Standards 
requirements when installed to  the 
dimensions in these Instructions. (They have 
been tested by an Independent Testing Lab).

Clamping Down the Cooktop

This cooktop is supplied with fastening 
clamps that will cope with a bench thickness 
of 20-50 mm.  For benchtops thicker than 50 
mm, recess the underside to a thickness of 
20-50 mm.

Gas Supply Connection

 

This cooktop is supplied set up for 
Natural Gas

 but is suitable for installation 

with either Natural Gas or LPG.  Refer to 
relevant table for pressures and appropriate 
orifice sizes. 

  Gas connection to the product MUST use 

the elbow supplied.  The regulator will not 
seal if installed without it.

  Ensure the blue washer (supplied) is located 

between the elbow (supplied) and product 
inlet as below.  Failure to use this washer 
will cause the product to leak.  Tighten the 
floating nut to firm finger tight, plus an 
additional 

1

/

4

 turn (90

o

).

    

 

After installation, make sure all 
connections are gas tight.

  A duplicate data plate enclosed inside the 

accessories pack should be placed on an 
accessible surface adjacent to the cooktop.

Flexible Hoses

  Flexible hose assemblies should be AS/NZS 

1869 Class B or Class D certified.

  Flexible hoses should not be exposed to 

temperatures exceeding their certified value.  
They should not touch hot surfaces on the 
cooktop or neighbouring products.

  Flexible hoses should not be subject to 

abrasion, kinking or permanent deformation.

Installation Instructions

20 mm

50 mm

recessed to 
50 mm

Blue washer

Elbow (

1

/

2

” BSP male)

Gas Inlet (

1

/

2

” BSP internal thread)

C

G

913 series

Summary of Contents for CG602 Series

Page 1: ...599257 A 01 2005 NZ AU Installation Instructions NZ AU CG913 SERIES CG602 SERIES CG902 SERIES...

Page 2: ...ation available to the person responsible for installing the product as it could reduce your installation costs These products are registered in New Zealand at www ess govt nz and in Australia with AG...

Page 3: ...s CG902 series CG913 series D Width 560 558 562 870 846 872 870 860 882 E Depth 490 485 495 494 478 501 494 486 524 F Radius R10 R10 R10 G 30 30 30 H 40 50 35 J Clearance to nearest combustible servic...

Page 4: ...ble surface 100 mm 90 mm 90 mm Clearance from rear edge of product to any non combustible surface 10 mm 10 mm 10 mm e Clearance below benchtop to any combustible surface 60 mm 60 mm 81 mm Clearance be...

Page 5: ...ll cope with a bench thickness of 20 50 mm For benchtops thicker than 50 mm recess the underside to a thickness of 20 50 mm Gas Supply Connection This cooktop is supplied set up for Natural Gas but is...

Page 6: ...heck insulation resistance and earth continuity Natural Gas For Natural Gas usage the gas supply is connected to the regulator which is supplied loose with a built in test point 1kPa 4 WG and the inle...

Page 7: ...knob 5 When the setting is right check regulation by quickly rotating the knob from the maximum to the minimum delivery position The flame must not go out figure 6 12 Turn on main electrical supply an...

Page 8: ...front 0 85 mm 3 7 MJ h 0 55 mm 4 1 MJ h Semi Rapid Burner LH RH rear 1 3 mm 7 9 MJ h 0 80 mm 7 9 MJ h Fish Burner Centre 1 45 mm 10 MJ h 0 85 mm 10 MJ h Wok Burner LH front 1 8 mm 15 MJ h 1 05 mm 15...

Reviews: