4 | Commissioning
FISCHER Mess- und Regeltechnik GmbH
14/28
BA_EN_ME50_ATEX
4.3 Parameters
After it has been switched on, the unit carries out a display test and shows the
implemented firmware version for approx. 2s. Then the pressure transmitter
switches to the operating mode.
Press the OK key
û
to enter the configuration mode.
During configuration, the parameter name or the parameter value is shown in-
stead of the measured value. The unit continues to work during configuration
and shows pressure changes in the bar chart display. Changes can be followed
directly without changing the operating mode.
NOTICE
Time out
If no key is pressed for a longer period (approx. 1 minute), the units switches
automatically into work mode.
Set parameters
Proceed as follows to set a parameter:
1. Press the enter OK key to switch to the configuration mode.
2. Use the arrow keys
ÿ þ
to navigate through the parameter list until you
reach the required parameter.
3. Press the enter OK key to call up the parameter. The parameter value is
shown.
4. Use the arrow keys
ÿ þ
to set the required parameter value.
5. Press the enter OK key to save the value. The parameter name is now
shown on the display.
6. Use the arrow keys
ÿ þ
to navigate through the parameter list until you
reach the required parameter.
7. Press the enter OK key
û
to leave to the parameter menu. The pressure
transmitter switches to the operating mode.