background image

FISCHER Mess- und Regeltechnik GMBH

Installation and assembly | 3

BA_EN_ME11

9/24

3.2.1 Measuring lines that need to be connected

The following points need to be observed when connecting the pressure line:

• To ensure there is no influence on the measured values, severe bends and

coils in the wire should be avoided.

• To prevent deposits, there should be a continuous incline or drop of at least

8%.

• When measuring steam pressure, a water bag-forming loop must be

provided due to the temperature (see accessories).

Round shape

U-shape

ca. 180

Ø20

56

155

ca. 200

ca. 275

ca. 130

Ø20

Ø56

AF27

Manometer connection

Connection spigot 
according to 
DIN EN 837-1

Fig. 6: 

Siphon MZ1###

• The transmitter must be positioned below the measuring point for liquid

measurements. Vent the pressure line before commissioning.

• The transmitter must be positioned above the measuring point for gas

measurements.

3.2.2 Pressure surge absorption

Pulsating pressure on the system side can lead to functional problems. We re-
commend installing a damping element in the pressure connection lines as a
protective measure.

a) Capillary throttle

Manometer connection

SW27

AF27

Connection spigot 

according to DIN EN 837-1

305

110

Ø88

Ø4

Fig. 7: 

Capillary throttle MZ400#

Summary of Contents for ME11 Series

Page 1: ...Operating manual ME11 Pressure Transmitter 09005184 BA_EN_ME11 Rev ST4 B 04 22 09005184...

Page 2: ...y other form print photocopy microfilm or another process without the written consent of the company FISCHER Mess und Regeltechnik GmbH Bad Salzuflen Reproduction for internal use is expressly allowed...

Page 3: ...ctogram explanation 5 2 Product and functional description 6 2 1 Intended use 6 2 2 Product summary 6 2 3 Function diagram 7 2 4 Design and mode of operation 7 3 Installation and assembly 8 3 1 Genera...

Page 4: ...s the work they have been assigned and recognize potential dangers by virtue of their specialized training their skills and experience and their knowledge of the pertinent standards 1 3 Risks due to N...

Page 5: ...ompany is responsible for ensuring that all required mainten ance inspection and installation work is carried out by qualified specialized per sonnel 1 8 Pictogram explanation DANGER Type and source o...

Page 6: ...essive media because the unit needs to be adapted for the specific customer in terms of the parts that come into contact with the media The device may only be used for the purpose stipulated by the ma...

Page 7: ...suring range Electr Output Operating voltage Prod no Silicone free Fig 3 Nameplate 2 3 Function diagram Pressure p R R U I U b out 1 2 3 4 5 Fig 4 Function diagram 1 Ceramic sensor 2 electronics 3 Aux...

Page 8: ...tion however any installation posi tion is possible To guarantee safe working conditions during installation and maintenance suit able stop valves must be fitted in the system see accessories By means...

Page 9: ...ape U shape G ca 180 20 56 155 ca 200 G G ca 275 ca 130 20 56 G AF27 Manometer connection Connection spigot according to DIN EN 837 1 Fig 6 Siphon MZ1 The transmitter must be positioned below the meas...

Page 10: ...1 Manometer connection Fig 8 Damping reactor MZ410 3 3 Electrical connections By authorized and qualified specialized personnel only When connecting the unit the national and international electro te...

Page 11: ...w connection M16x1 5 Seal NBR Contact insert Housing Screw 1 2 3 Line socket Flanged connector Fig 11 Line socket DIN EN 175 301 803 A Ter minal Signal name DC Cable colour 1 Supply Output Ub Sig red...

Page 12: ...utput Sig Black Table 4 3 wire connection 0 10V 3 4 Commissioning All electrical supply operating and measuring lines and the pressure connec tions must have been correctly installed before commission...

Page 13: ...evices should be sent directly to our repair department Please coordinate all shipments with our sales department WARNING Process media residues Process media residues in and on dismantled devices can...

Page 14: ...0 2500 kPa 100 bar 150 bar 0 40 bar 0 4000 kPa 100 bar 150 bar 0 60 bar 0 6000 kPa 200 bar 250 bar Vacuum and measuring ranges Measuring range Pressure safety SI unit Overpres sure Bursting pressure 1...

Page 15: ...5 W VA 5 6 Operating conditions Ambient temperature range 0 C 60 C Storage temperature range 20 C 85 C Medium temperature range 0 C 85 C EMC EN 61326 1 2013 EN 61326 2 3 2013 RoHS EN 50581 2012 Type...

Page 16: ...EN_ME11 5 7 Construction design 5 7 1 Standard casing dimensional drawing All dimensions in mm unless otherwise stated M12 x 1 72 38 5 28 SW27 91 20 3 G 6 17 5 13 2 5 G 9 5 20 18 NPT EXT SW27 Schrader...

Page 17: ...th external thread 5 7 3 Electrical connections Fig 14 Line socket DIN EN 175 301 803 A Unit connector and cable socket DIN EN 175 301 803 Form A 4 pin 1 3 2 1 2 3 Line socket Device plug 1 2 2 Wire 3...

Page 18: ...5 6 7 8 9 10 11 12 3 4 Code no Measurement accuracy 1 2 Measuring range 01 0 0 6bar 02 0 1bar 03 0 1 6 bar 04 0 2 5 bar 05 0 4bar 06 0 6bar 07 0 10bar 08 0 16bar 09 0 25bar 10 0 40bar 11 0 60bar 31 1...

Page 19: ...B 4 20 mA DC 2 Wire 24V DC C 0 10 V DC 3 Conductor 24 V AC DC 7 Electrical connection H 4 pin standard plug DIN EN 175 301 803 A M 4 pin M12 plug connection DIN EN 61076 2 101 8 Operating voltage 9 24...

Page 20: ...11 6 1 Prefabricated connection lines Order no Designation No of Poles length 06401993 PUR cable with M12 coupling 4 pin 2m 06401994 PUR cable with M12 coupling 4 pin 5m 06401563 PUR cable with M12 co...

Page 21: ...FISCHER Mess und Regeltechnik GMBH Attachments 7 BA_EN_ME11 21 24 7 Attachments Fig 16 CE_EN_ME11...

Page 22: ...7 Attachments FISCHER Mess und Regeltechnik GMBH 22 24 BA_EN_ME11 Fig 17 UKCA_EN_ME11...

Page 23: ...FISCHER Mess und Regeltechnik GMBH BA_EN_ME11 23 24 Notes...

Page 24: ...lefelder Str 37a D 32107 Bad Salzuflen Tel 49 5222 974 0 Fax 49 5222 7170 www fischermesstechnik de info fischermesstechnik de Technische nderungen vorbehalten Subject to technical changes Sous r serv...

Reviews: