4 | Commissioning
FISCHER Mess- und Regeltechnik GmbH
20/36
BA_EN_DE49_A
i g1
lower current limit
Define the minimum output signal here (3.5 ... 22.5mA).
i g2
upper current limit
Define the maximum output signal here (3.5 ... 22.5mA).
i er
Error signal
Define the output signal here (3.5 ... 22.5mA) that should be issued when there
is an internal error in the device.
pass
Password
A value between 1 and 999 can be selected for the password. The value 0 de-
activates the password function.
rst
Reset
This parameter value is set to 0. If this parameter is set to 1, all parameters are
irrevocably reset to the default settings.
ESc
menu end
(OUTPUT)