FISCHER Mess- und Regeltechnik GmbH
Commissioning | 4
BA_EN_DE49_A
19/36
F
Function selection
• F=0
The device works as a linear transmitter. The parameters marked in red and
blue are hidden.
• F=1
causes a rooting of the output signal and the display.. The parameters
marked in red (dPF, MAF, MEF, MEd) and shown.
• F=3 … 30
causes linearization of the output and display based on a support point
table. The parameter F states the number of support points (value pairs) in
the table. The table can contain 3 to 30 support points. If the table is used,
the parameters marked in red and blue (dPF, MAF, MEF, MED and LIN) are
shown. The measured value is displayed without a unit and can therefore
be assigned to any unit by the user using the additional parameters (free
unit).
The measured value is displayed without a unit and can therefore be assigned
to any unit by the user using the following parameters (free unit).
dPF
Decimal point „free unit“
This parameter states the number of decimal points of the displayed measured
value. Possible values are 0…3.
maf
Start of measuring range "free unit"
Defines the start of the free measuring range. (This value can normally stay at 0
for a filling level measurement)
mef
End of measuring range 'free unit'
Defines the end of the free measuring. Maximum value: 9999.
Med
Fluid
This parameter is specially designed for measuring contents. The medium used
is important when calculating the contents.
0
Water
1
Petrol
2
Diesel
NOTICE! The support point table must always be created for filling levels
with water!
lin
Support point table
Define the support point table here.
end
i-01
p-01
i-02
p-02
i-03
p-03
i-30
p-30
Value pair 1
Value pair 2
Value pair 3
Value pair 30
Sub menu
Summary of Contents for DE49 A Series
Page 27: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_DE49_A 27 36 ...
Page 33: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE49_A 33 36 Notes ...
Page 34: ...FISCHER Mess und Regeltechnik GmbH 34 36 BA_EN_DE49_A Notes ...
Page 35: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE49_A 35 36 Notes ...