background image

6

5.3.8. Look-up Table Programming (F = 3..30)

If the value of set-up parameter 

F

 is selected equal to or

greater than 3, a sub-menu 

LIn

 is invoked. Through this

sub-menu  all  the  required  look-up  table  values  can  be
entered, except the first and last pairs of table values (re-
spectively corresponding to 

MA

 and 

ME

). This sub-menu

has its own entry and exit points, the latter being the last
of the value pairs to be entered. The table is stored only
when the user exits to the sub-menu prompt 

LIn

, by pres-

sing 

û

. If the table is not correctly entered, the display

will indicate 

Err

, indicating an error condition. If this hap-

pens, it is not possible to exit this sub-menu mode until
the error is corrected.

The table entries consist of 1 to 28 pairs of values. Valu-
es 

I02

  through 

I29

  (or 

u02

  through 

u29

)  specify  the

amplitude of the signal output, and the values 

P02

 throu-

gh 

P29

 are the corresponding pressure values.

Entering  or  changing  table  values  through  the  instru-
ment's membrane keyboard is a tedious and error-prone
method.  It  should  only  be  used  as  a  stopgap  method
when a PC and/or the PC Interface Module is not availa-
ble.

The table is accepted as correct if each output value is
larger than its preceding value. Pressure values can be
steadily  increasing  or  steadily  decreasing.  However,  a
transition from falling to rising pressure values is not per-
mitted; nor are pressure values allowed to turn back alo-
ng the same curve.

5.3.9. Limit Setting

The  two  limit  switching  outputs 

  (relay  contacts  or

solid-state switches) are each configured by four set-up
parameters: 

Switching  output  1  is  configured  by  parameters 

R1A,

R1E, R1D

 and 

R1F

Switching  output  2  is  configured  by  parameters 

R2A,

R2E, R2D

 and 

R2F

.

The turn-on and turn-off points of switching output 1 are
defined  respectively  by  parameters 

R1A

  and 

R1E

.  The

values for these are set in the currently valid unit of mea-
surement (indicated by the lighted symbol to the right of
the digital display).

The two parameters 

R1A

 and 

R1E

 together determine the

logic of switching output 1:

If 

R1A

 is smaller than 

R1E

, the output turns on when the

measured  value  exceeds 

R1E

.  It  turns  off  again  only

when  the  measured  value  falls  below 

R1A

  (hysteresis

function).

If 

R1A

 and 

R1E

 have the same value, there is no hystere-

sis: the switching output turns on when the measured va-
lue  exceeds 

R1A

  / 

R1E

,  and  turns  off  again  when  the

measured value falls below 

R1A

 / 

R1E

.

If 

R1A

 is  larger than 

R1E

,  the  switching  output  turns  on

when  the  measured  value  falls  between 

R1A

  and 

R1E

:

i.e.,  when 

R1E

  <  measured  value  < 

R1A

  (window  limit

function).

Both parameters can be independently adjusted over the
full measuring range.

If  the  unit  of  measurement  is  changed,  the  switching
points are changed accordingly. In this  event,  rounding
error can cause a deviation in the least significant (right-
most) digit.

The  value  of  the  set-up  parameter 

R1D

  determines the

delay time for switching output 1, after the measured va-
lue reaches the switching point. The delay value can be
selected in the range 0.0 to 100.0 secs. This value app-
lies equally to turn on and turn off.

The  set-up parameter 

R1F

  determines  the action of the

switching output. If 

R1F

 = 1, the switching output acts as

normally open (NO) contacts. If 

R1F

 = 2, it acts as nor-

mally closed (NC) contacts.

5.3.10.Password

The  last set-up parameter  allows a password to be en-
tered. A password value of 001 to 999 can be selected.
A value of 000 disables the password function.

If a password was set previously the digital display indi-
cates 

PAS

 after 

Esc

 is displayed and 

û

 is pressed. The

password  is  then  entered, by  pressing 

û

  and then 

þ

,

ÿ

. Only then will the set-up menu options be accessible.

If  an  incorrect  password  is  entered,  the  display  jumps
back to beginning of the menu (i.e., 

Esc

).

New Functions! (as of April 2008)

5.3.11.

 D0

– Display options

This parameter allows smoothing the displayed values in
cases  where  they  are  frequently  deviating.  The  filter
function is similar to the 

dAM

 function, but acts only upon

the display, having no impact on the output signal. Addi-
tionally the display  can be  turned off  partially (

D0

 = -1,

only  the  setpoint  LEDs  are  driven)  or  completely
(

D0

= -2).

5.3.12.

 res

– Reset to default values

This function will reset all parameters to default when ac-
tivated. Default values can be defined only by using the
PC interface.

5.3.13. 

MAF, MEF, dPF

– Free Unit

If the device is configured to have a “free“ third unit (sym-
bol: 

)  then  the  display  can  be  scaled  as  desired  by

using these three parameters.

The measuring range as defined by parameters

MA

and

ME

is rescaled to 

MAF

 and 

MEF

. If the table function ( 

F

)

is  enabled,  table  values  will  be  taken  into  account  too.
The 

dPF

 value controls the position of the decimal point.

Contact: EK Engineering (India)
Web: www.ekeindia.com
Email: [email protected]

Summary of Contents for DE44 KR Series

Page 1: ...tallation operation maintenance and inspection of this product must have the qualifications training and experience necessary to carry out such work on this type of equipment Qualified personnel are people who are able to judge delegated work and possible dangers due to technical education proficiency and experiences and especially by knowledge about the relevant norms When working with explosion ...

Page 2: ...oduct if and as necessary should be done only by Fischer Mess und Regeltechnik GmbH 1 6 Operational Restrictions The operational reliability of the product is guaranteed only when used for intended purposes The product must be selected and configured for use specifically with defi ned process media The limiting values of operating pa rameters as given in the product specification sheet must never ...

Page 3: ...hazardous areas e g EN 60079 14 EN 50014 Operating supply voltage 24 V DC AC must not excess 32 V DC AC neither per temporary inter ferences Supply wiring system must be protec ted by Si 315 T For recommended current supply see 11 Specifi cations Parametrisation by PC serial interface adaptor EU03 F300 is permitted only in safe areas outside explosion hazardous areas zone 2 5 Commissioning Power s...

Page 4: ...s again û to store the selection and EIN will appear again in the digital display To exit the set up mode press ÿ until ESc appears and then press û The current pressure measured value is indicated again and the appropriate symbol of the unit of measurement to the right of the digital display is lit The digital display is limited to a count of 1999 Therefore all the available units of measurement ...

Page 5: ... oG2 and oEr specify the limits of the signal output current or voltage that are not to be exceeded irrespective of the actual pressure These limit values have higher priority than the MA and ME pressure span settings These settings serve mainly to prevent control systems from interpreting brief pressure excursions outside the measuring range as error fault events oG1 sets the out put signal minim...

Page 6: ...tput turns on when the measured va lue exceeds R1A R1E and turns off again when the measured value falls below R1A R1E If R1A is larger than R1E the switching output turns on when the measured value falls between R1A and R1E i e when R1E measured value R1A window limit function Both parameters can be independently adjusted over the full measuring range If the unit of measurement is changed the swi...

Page 7: ...easuring range start point The value of the measured variable corresponding with the mi nimum value of the output signal 0 V 0 mA or 4 mA depending on the instrument version ME Measuring range end point The value of the measured variable corresponding with the ma ximum value of the output signal 10 V or 20 mA depending on the instrument version dPF Position of decimal place for free unit MAF Measu...

Page 8: ...htness Check the integrity of all electrical connections of the instruments Inspection and test schedules depend on operating and site conditions The operating manuals of other equip ment to which the transmitter is connected must be read thoroughly to ensure that all of them work correctly when connected together 7 Transport The product must be protected against shock and vibra tion during transp...

Page 9: ...9 11 Specifications 11 1 General Two independent differential pressure sensors Contact EK Engineering India Web www ekeindia com Email india eke gmail com ...

Page 10: ...e for signal output display seperated Display function 0 0 Pressure port 1 only 0 1 Pressure port 2 only 0 2 25 5 Display alternating time 0 Relay switch 1 2 Activation point de activation point response time delay 0 0 100 0 secs logic N O or N C Measurement unit selection mbar Pa free unit start value end value and decimal place for free unit Zero suppression 0 100 counts 1 Output signal start en...

Page 11: ... mbar 5 8 0 100 mbar 500 mbar 5 9 2 5 2 5 mbar 50 mbar A 6 4 4 mbar 50 mbar A 7 6 6 mbar 100 mbar A 8 10 10 mbar 100 mbar A 9 16 16 mbar 250 mbar B 1 25 25 mbar 250 mbar B 2 40 40 mbar 500 mbar C 5 60 60 mbar 500 mbar B 3 Pressure Connections Threaded hose clamp connectors for 6 4 mm hose 4 0 Threaded hose clamp connectors for 8 6 mm hose 4 1 Signal Output Pressure Port I only No signal output 0 C...

Page 12: ...switch 2 m 06401994 Cable with M12 connector 4 pin for switch 5 m 06401995 Cable with M12 connector 5 pin for supply signal 2 m 06401996 Cable with M12 connector 5 pin for supply signal 5 m 04005144 Wall mounting adaptor plate EU03 F300 PC programming interface with SW Contact EK Engineering India Web www ekeindia com Email india eke gmail com ...

Reviews: