3.2 Electrical connection
3.2.1 Power supply connections
The electrical connection of the condensing unit to the power supply must be made by qualified
technicians according to the valid electrical directives, for instance DIN EN 60204-1. Also the
voltage drop and temperatures on line must be considered for cable selection.
The [ CF ] EASY units are designed for a 380-420V / 3Ph / 50 Hz power supply for TFD and
220-240V / 1Ph / 50 Hz for PFJ. A voltage tolerance of ± 10% is acceptable.
The circuit breaker must be switched off before opening the front door.
WARNING
Electrical shock hazard! Serious personal injuries!
There are unused
fast-on pins (
C1
&
D02
) on the XCM25D which could be under voltage. They
are covered by insulated fast-on flags in the factory. Handle carefully when
removing insulating flags during service on site.
3.2.2 Maximum operating currents for cable selection
Unit model
Maximum operating
current A
CFME Medium temperature standard TFD three phase
CFME-020-TFD
4.9
CFME-030-TFD
7.2
CFME-040-TFD
10.3
CFME-050-TFD
12.8
CFME-060-TFD
13.1
CFME-075-TFD
14.0
CFME Medium temperature standard PFJ single phase
CFME-020-PFJ
12.8
CFME-025-PFJ
12.4
CFME-030-PFJ
16.4
CFME-040-PFJ
23.5
CFDE Medium temperature Digital TFD three phase
CFDE-040-TFD
7.9
CFDE-050-TFD
11.3
CFDE-060-TFD
11.4
CFDE-075-TFD
14.0
CFLE Low temperature TFD three phase
CFLE-020-TFD
5.7
CFLE-030-TFD
6.7
CFLE-040-TFD
9.2
CFLE-050-TFD
11.9
CFLE-060-TFD
13.7
CFLE-075-TFD
14.6
Table 21: Maximum operating currents for cable selection
3.2.3 Electrical wiring
Before commissioning, ensure that the neutral "N" and ground protection “PE” wires are
connected to the main switch.
3.2.4 Electrical protection standard (protection class)
Scroll compressors up to ZX51: IP21 according to IEC 34.
Fan: IP44 according to IEC 34.
Solenoid valve coils: IP65 according to DIN 43650.