UNI TEMP 

Settings:

1

ON

2 3 4

DIP switch settings

CW

Temperature 

range setting

x10

CCW

x1

1

2

3

4

min

max

DIP

0

°

C..100

°

C

60

°

C..85

°

20

°

C..70

°

C 25

°

C..45

°

C

2

OFF

OFF

ON

ON

3

OFF

ON

OFF

ON

Temperature range setting

1

ON

2 3

4

Xp parameter 

a proportional control 

range of valve

With DIP switches inside actuator 
is possible to set the following 
parameters:

DIP 1

Direction of rotation (direct CW / 
inverse CCW)

DIP 2,3 Different temperature ranges 

depending on the application 
(0°C..100°C, 60°C..85°, 20°C..70°C, 
25°C..45°C)

DIP 4

Reaction factor

NOTE – when changing DIP1 position, 
controller calibration is carried out

DIP switches and trimmer Xp are located 
inside controller. To open the controller it is 
necessary to loosen the screws on the cover 
(3x), and handle screw (1x).

LED indication of operation:
- Blinking – controller calibration
- ON: normal operation

Xp parameter - a proportional control range 
of valve (from 10K to 100K)

ON

1 2 3 4

MAN

AUTO

8 8 8

1 Mechanical  indication.

Indicator can be set according to the valve assembly

2 Button for manual/auto control

3 Handle for manually controlling the drive, which also serves for the 

indication position of the valve

4 Button for adjusting the required temperature. When adjusting the 

temperature, the set value flashes on LCD screen.

5 LCD screen for displaying temperature

UNI TEMP 

www.first.si

5

Recommended mounting position

Manual control:

Note: 

when the button 

for manual operation is 
in <MAN> position, 
controller stays in 
temporary position 
irrespective of control 
signal.

Controller behavior diagram as a function of temperature:

50

45

45°C

50°C

55°C

55

permanent 

valve opening

permanent 

valve closing

set temperature

T (°C)

t

closing area

100% opening

100% closing

opening area

T

50

=

set

°C

Xp =10K

Xp = 10K

permanent 

valve opening

permanent 

valve closing

impulse valve 

opening

impulse valve 

closing

Example:

-

Desired temperature: 50 C

-

Xp parameter – proportional control range of valve (10K)

°

When the temperature is 
less than 45

, controller 

gives continuous signal 
for opening mixing valve.

°C

When the temperature is 
between 45

 and 50

controller pulsating 
opens mixing valve. 
Nearer the desired 
temperature (50

), 

shorter pulses.

°C

°C

°C

When the temperature is 
between 50

 and 55

controller pulsating 
closes mixing valve.
Nearer the desired 
temperature (50

), 

shorter pulses.

°C

°C

°C

When the temperature is 
higher than 55

controller gives 
continuous signal for 
closing mixing valve.

°C

Nearer the desired 

temperature (50

), 

shorter pulses.

°C

Nearer the desired 
temperature (50

), 

shorter pulses.

°C

impulse valve 

opening

impulse valve 

closing

90°

90°

90°

90°

ON

1 2 3 4

FIRST
UNI MRB

LED

COM

Xp

Summary of Contents for UNI TEMP

Page 1: ...ting kit FIR T ROTOMIX ROTOMIX G ESBE VRG VRB ACASO TERMOMIX BARBERI FEROTERM PAW EURONORM ESBE IMP DANFOSS BESSER SELTRON LOVATO TUXHORN STRAWA CIMBERIO UNI TEMP is a constant temperature controller...

Page 2: ...ort Caution power supply voltage 24VAC It may only be installed by suitably trained personnel All applicable legal or institutional installation regulations must be complied with The device must be pr...

Page 3: ...it Code Enclosed mounting kit 58024 VRG VRB ACASO TERMOMIX BARBERI FEROTERM PAW EURONORM ESBE IMP DANFOSS BESSER SELTRON LOVATO TUXHORN STRAWA CIMBERIO By special request 58025 SELTRON LOVATO PAW 5802...

Page 4: ...controller calibration is carried out DIP switches and trimmer Xp are located inside controller To open the controller it is necessary to loosen the screws on the cover 3x and handle screw 1x LED ind...

Page 5: ...Example Desired temperature 50 C Xp parameter proportional control range of valve 10K When the temperature is less than 45 controller gives continuous signal for opening mixing valve C When the temper...

Page 6: ...UNI TEMP UNI TEMP UNI TEMP UNI TEMP DTC100 2 M Examples UNI TEMP M UNI TEMP ROTOTERM MR TR Maintain a constant temperature in sanitary water circuit Floor heating Maintain a constant temperature of he...

Page 7: ...rements for CE conformity marking according to the following directives EMC directive 2004 108 EEC LV directive 2006 95 EEC PAH directive 2005 69 EEC In compliance with standards EN 60730 2 14 1997 A1...

Reviews: