BATTERY WATER
Water used for topping up batteries must comply with the following specifications:
• It shall be clear, colourless and odourless.
• The pH shall be between 5 and 7.
• Impurities shall not exceed the limits below.
• It shall, wherever possible, be stored in a glass or plastic container.
• Conductivity shall be less than 30 μS/cm
IMPURITY
MILLIGRAMS
PER LITRE
DISSOLVED SOLIDS
25
ARSENIC (As)
1
CHLORIDE (Cl)
5
COPPER (Cu)
0.1
IRON (Fe)
0.2
MANGANESE (Mn)
0.1
NITROGEN (as NH
4
)
5
NITROGEN (as NO
3
)
5
HEAVY METALS (as Pb)
5
KMn0
4
REDUCING SUBSTANCES
*
10
*As determined by F.N.B. test method LTM - 31 -01
TROUBLE SHOOTING
The following notes are provided to assist in identifying symptoms and causes of
possible system problems.
SYMPTOMS
CAUSES
SOLUTIONS
Low or irregular voltages
Undercharge. Faulty Reset regulator
and/or specific gravity.
regulator settings.
settings.
.
Battery requires
Apply equalise charge.
equalise charge.
Undercharge.
Install more panels or
Insufficient solar
reduce load.
panels to recharge.
Overdischarge. System
Reduce load or
undersized for the load.
increase capacity.
Faulty cell/s.
Replace cell/s unless
battery is near end of
life.