FAN COIL UNIT

4

HBC(X), PHBC(X), RHBC(X), CHBC(X)

Installation, Operation, and  Maintenance  Instructions

FAN COIL UNIT 

The installer must adhere strictly to all local and national code requirements 
pertaining to the installation of this equipment. These units are designed for 
installation in a horizontal position above a dropped ceiling. All units are 
designed for indoor use only, and are agency listed for installation with zero 
clearance to combustible materials. This includes the fan coil cabinet, 
discharge plenum and connecting ducts.
Free return installation (non-ducted return air): The furred down area must be 
completely sealed (except return air grille) to ensure that all return air is pulled 
from the conditioned space and not from other areas of the building structure.
Access must be provided for servicing the unit. If this access is provided by a 
removable ceiling panel, ample space must be allowed for removal of the 
blower panels and to provide access to electrical and plumbing controls. 
When required, the unit can be tilted toward the drain nipple to ensure proper 
drainage.

NOTES:

•  

A field-fabricated secondary drain pan, with a drain pipe routed to the 

outside of the building, may be required in installations over a finished 
living space or in any area that may be damaged by water overflow from 
the main drain pan. In some localities local codes may require a secondary 
drain pan for any horizontal installation.

If a condensate overflow shut off switch, that is designed to be installed in 
the drain line, is used in place of a secondary drain line then place it in the 
primary drain line between the fan coil and the P-trap.

MOUNTING

It is important to ensure fan coils are securely mounted and the structure is 
sufficient to support the weight of the equipment. All anchors for mounting 
equipment must be placed and sized to ensure a safe and durable installation.
These units are provided with six (6) mounting slots. Metal washers and nuts of 
the proper size are to be provided by the installer. When necessary, use shims 
to obtain the proper level to ensure condensate will drain from the unit.
If mounting to wooden joists, use as a minimum 1/4” x 2” wood screws fully 
engaged with fender washers for securing this unit to the structure.

Summary of Contents for 450532L 5HBC32 LH

Page 1: ...or local codes in any way These instructions must be left with the property owner SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire...

Page 2: ...death When fan coil is operating some components are operating at high speeds Personal injury can result from touching these items with any object All electrical and service access panels must be sec...

Page 3: ...tion exists prior to energizing any power sources Always review the nameplate and wiring diagram on each unit for proper voltage and control configurations This information is determined from the comp...

Page 4: ...be tilted toward the drain nipple to ensure proper drainage NOTES A field fabricated secondary drain pan with a drain pipe routed to the outside of the building may be required in installations over a...

Page 5: ...Disconnect all power supplies before servicing lock out tag out to prevent accidental electrical shock Note there may be multiple power sources Use copper conductors only Install all parts and panels...

Page 6: ...s Damage can occur in the form of excessive heat build up and interference to the operation and moving parts will result 10 All piping made in the field should be installed with consideration of addit...

Page 7: ...return air space is large enough that a negative pressure is not present however a trapped condensate line is recommended in case a negative condition should occur the unit would drain properly PIPING...

Page 8: ...8 HBC X PHBC X RHBC X CHBC X Installation Operation and Maintenance Instructions FIGURE 1 Determination of Right Hand Left Hand References FIGURE 2 Coil Assemblies Right Hand Shown 3 2 Row 3 1 4 1 3 R...

Page 9: ...r valves ceiling wall plenum or other accessories 3 All valves will operate at any angle with the exception of the motorized valve which must never be installed with the power head below horizontal Th...

Page 10: ...am that is supplied with the unit Failure to do so could result in damage to components and will void all warranties Prior to starting the unit 1 Ensure supply voltage matches nameplate data 2 Ensure...

Page 11: ...e filter with the same type as originally furnished COIL Any dust or other contaminants which accumulate on the heat transfer surfaces interferes with the air flow and impairs heat transfer The coil m...

Reviews: