First Co 450532L 5HBC32 LH Installation, Operation And Maintenance Instructions Download Page 3

INSTALLATION PRECAUTIONS

HBC(X), PHBC(X), RHBC(X), CHBC(X):

 

Installation, Operation, and Maintenance Instructions

3

applicable regulations take precedence over the general instructions contained 
in this manual.

INSTALLATION PRECAUTIONS

  

WARNING:

Some units are very heavy. Use two or more people when moving and 
installing these units. Failure to do so could result in personal injury or 
death. Contact with metal edges and corners while applying excessive 
force can result in personal injury. Use gloves when handling equipment. 
Use caution during installation or while servicing equipment.
Installation of this fan coil should be performed only by a licensed contractor to 
ensure proper installation and the safety of the installer. Observe the following 
precautions for typical installations:

Always use proper tools and equipment.

No wiring or other work should be attempted without first ensuring fan coil 
is completely disconnected from the power source and locked out. Always 
verify that a good permanent, uninterrupted ground connection exists 
prior to energizing any power sources.

Always review the nameplate and wiring diagram on each unit for proper 
voltage and control configurations. This information is determined from the 
components and wiring of the unit and may vary from unit to unit.

When soldering or brazing to the unit, it is recommended to have a fire 
extinguisher readily available. When soldering close to water valves or other 
components, heat shields or wet rags are required to prevent damage.

When the fan coil unit is in operation components are rotating at high 
speeds.

Units must be installed level or angled toward the drain nipple to ensure 
proper drainage and operation.

Check unit prior to operation to ensure that the condensate water will drain 
toward the drain connection. An overflow drain or an auxiliary drain pan 
under the fan coil may be required as a back up to a clogged primary drain.

Be sure that the drain pan is free from foreign material prior to start up.

Check filter media installation to ensure that it is installed correctly.

 Use the directional arrows or other information on the filter to determine 
the proper flow direction.

Ensure air distribution system does not exceed the external static rating of 
the unit.

Summary of Contents for 450532L 5HBC32 LH

Page 1: ...or local codes in any way These instructions must be left with the property owner SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire...

Page 2: ...death When fan coil is operating some components are operating at high speeds Personal injury can result from touching these items with any object All electrical and service access panels must be sec...

Page 3: ...tion exists prior to energizing any power sources Always review the nameplate and wiring diagram on each unit for proper voltage and control configurations This information is determined from the comp...

Page 4: ...be tilted toward the drain nipple to ensure proper drainage NOTES A field fabricated secondary drain pan with a drain pipe routed to the outside of the building may be required in installations over a...

Page 5: ...Disconnect all power supplies before servicing lock out tag out to prevent accidental electrical shock Note there may be multiple power sources Use copper conductors only Install all parts and panels...

Page 6: ...s Damage can occur in the form of excessive heat build up and interference to the operation and moving parts will result 10 All piping made in the field should be installed with consideration of addit...

Page 7: ...return air space is large enough that a negative pressure is not present however a trapped condensate line is recommended in case a negative condition should occur the unit would drain properly PIPING...

Page 8: ...8 HBC X PHBC X RHBC X CHBC X Installation Operation and Maintenance Instructions FIGURE 1 Determination of Right Hand Left Hand References FIGURE 2 Coil Assemblies Right Hand Shown 3 2 Row 3 1 4 1 3 R...

Page 9: ...r valves ceiling wall plenum or other accessories 3 All valves will operate at any angle with the exception of the motorized valve which must never be installed with the power head below horizontal Th...

Page 10: ...am that is supplied with the unit Failure to do so could result in damage to components and will void all warranties Prior to starting the unit 1 Ensure supply voltage matches nameplate data 2 Ensure...

Page 11: ...e filter with the same type as originally furnished COIL Any dust or other contaminants which accumulate on the heat transfer surfaces interferes with the air flow and impairs heat transfer The coil m...