Page 12
English
Ground Terminal
– Consult an electrician
for local grounding regulations.
9
10
11
120/240V, 50A
– (NEMA 14-50R)
Supplies electrical power for the operation of
120/240 Volt AC, 50Amp, single phase.
Maximum full load current may be drawn from
this receptacle. If other receptacles are used
at the same time, total power used must be
kept within nameplate.
Outlet Cover -
Protect
the
receptacles from
dust and debris.
LPG Hose Connector(Inlet) –
Used to connect
LPG hose
to generator.
12
120VAC, 20AMP GFCI RECEPTACLE
This unit is equipped with a ground fault circuit
interrupter (GFCI). This device meets applicable
federal, state and local codes .
A GFCI receptacle does NOT protect against
circuit overloads, short circuits, or shocks. For
example, electric shock can still occur if a person
touches charged electrical wires while standing
on a non-conducting surface, such as a wood floor.
Definition: Instead of following its normal safe
path, electricity passes through a persons body
to reach the ground. For example, a defective
appliance can cause a ground fault.
A GFCI receptacle is different from conventional
receptacles. In the event of a ground fault, a GFCI
will trip and quickly stop the flow of electricity to
prevent serious injury.
1. Plug a test lamp into the receptacle.
2. Start the generator, the test lamp should be on.
3. Press the “Test” button located on the front
of the receptacle to trip the device.
4. This should stop the flow of electricity making
the lamp shut off. The GFCI’s indicator light comes
off.
RESET
TEST
T
E
S
T
M
O
N
T
H
L
Y
F
O
L
L
O
W D
IR
E
C
T
IO
N
S
RESET BUTTON
Receptacle
Outlet
LED Indicator Light
TEST BUTTON
Outlet
5. To restore the flow of electricity, press the
“
RESET
” button on the front of the receptacle.
If the GFCI does not perform in this manner, do
not use the receptacle. Contact a local service
dealer or costumer service.
6. This outlet is protected against overload by
a 20A push-to-reset circuit breaker. Use the
outlet to power 120V AC, single-phase, 60 Hz,
electrical loads requiring up to a combined
2400 watts (2.4 kW) or 20 amps of current.
Testing the GFCI: Test the GFCI outlet every
month as follows:
SELF-TEST OPERATION
A Self-Test GFCI receptacle has all the features
of a conventional GFCI receptacle. In addition,
this receptacle tests itself periodically to confirm
the GFCI electronics are functional. The Indicator
Light will be solid green when the GFCI is powered
from Line side and working correctly.
Self-Test Indications
: If the Indicator Light is solid
orange or flashing red a problem may exist.
Press the TEST button to trip the GFCI. If unable to
Reset, replace the GFCI.