2

CUSTOMIZING E300 MESSAGES

The user can customize the lockout alarm message associated with each pair of terminals of the E300
Expansion Module. Each customized message can be up to 40 characters in length.

Note: Messages longer than 16 characters in length will scroll across the ED510 display. Messages
longer than 8 characters will scroll across the ED500 display. 

The following equipment is required:

An IBM compatible PC with E300 programming software (available on the E700 or E720 soft-
ware programs).

EC485 (RS232 to RS485 converter with power supply).

An ED512-2, -4, or -8 cable.

EP programmer with an Engineering code of 28 or later.

1.

Connect the EC485 converter to the serial COMMunication port of the IBM PC using an 
appropriate serial communications cable. Depending on whether the IBM PC has a 9-pin or a
25-pin serial communications port, the cable should be configured as follows:

CABLE CONNECTIONS, DB25 to DB25

 CABLE CONNECTIONS, DB25 to DB9

2.

Connect the ED612 (RJ12 female connector provided with the EC485) to terminals TD(A), TD
(B), RD(A), and RD(B) on the EC485. The pins on the ED610 will line up with the terminals on
the EC485 converter.

3.

Set the jumpers on the EC485 converter to 

SD

 and 

ECHO OFF

. See diagram below.

4.

Plug on end of the ED512-2, -4, -8 cable into the RJ12 jack on the ED612, and the other end into
either of the RJ12 jacks on the EP programmer.

5.

Hook up power supply 61-6689 to +12V and GND. White stripe wire is (+) lead.

The Flame-Monitor control must be powered, and the operating control (L1-13) should be open.
For complete details on customizing the E300 lockout messages, refer to Bulletin E-3001.

8

1

3

2

2

3

20

4

7

5

6

6

4

7

5

8

22

9

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

20

20

TO IC485
Converter

To IBM PC

TO IC485
Converter

To IBM PC

DB25(M)

DB9(FM)

DB25(FM)

DB25(M)

RS

-485

RS-232

FR. GRD

SHLD
TDA (-)

TDB (+)

RDA (-)

RDB (+)

+12VDC

GND

ECHO

ON

OFF

RTS

SD

CONTROL

TD

RD

ED512, -2, -4, -8

TO RJ12 CONNECTOR
ON EP PROGRAMMER

TO SERIAL
COMM PORT
ON IBM PC

ED612

WHITE STRIPE (+) LEAD

12 VDC POWER SUPPLY

61-6689

120 VAC
50/60HZ

(Approx 3/4” Thick)

2 1/8”

3 3/8”

Summary of Contents for EC485

Page 1: ...ack mounted on a PC board to provide an easy method to use the ED512 cables to interface to the EP programmers when customizing E300 mes sages The EC485 also includes a 120 VAC to 12 VDC power supply RS 485 Driver Control RTS SD Jumper The RS 485 side of the converter must be enabled to transmit data and disabled when not transmit ting Via a jumper on the converter either RTS or SD is selected as ...

Page 2: ... CABLE CONNECTIONS DB25 to DB9 2 Connect the ED612 RJ12 female connector provided with the EC485 to terminals TD A TD B RD A and RD B on the EC485 The pins on the ED610 will line up with the terminals on the EC485 converter 3 Set the jumpers on the EC485 converter to SD and ECHO OFF See diagram below 4 Plug on end of the ED512 2 4 8 cable into the RJ12 jack on the ED612 and the other end into eith...

Page 3: ...in wiring configuration The Fireye communication software program P N E720W is required for communication with the E340 controls Fireye recommends using the E500 Communication interface when communicating with the E340 controls since the E500 provides communication with the Flame Monitor flame safeguard con trols as well However the EC485 converter can be used to communicate only with the E340 con...

Page 4: ...YE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided In no event shall Fireye be liable for consequential or special damages of ...

Reviews: