DESCRIPTION

The Model 95DISP-1 and 95DISP-1-SS are two-line by sixteen-character alpha-numeric Vacuum-
Fluorescent Displays (VFD) with a five-pushbutton keypad. The 95DISP-1 is installed by the user
onto the end of the standard scanners. The 95DISP-1-SS is factory installed into the 95DSS3-
1CEXSS and 95DSS3-1CEX-2 scanners.

The Model 95WIDISP-2 is an Infrared Transmitter Module with four LED indicators for use with the
95DSS3 InSight II flame scanner.  Once installed, the user then programs the 95DSS3 via a remote
95WIHH-2 Wireless Handheld Commissioning Tool, ordered separately.  Refer to bulletin 133-735
for additional details.

The Model 61-7347-1 Blank Cover must be installed to maintain environmental ratings when neither
the 95DISP-1 nor 95WIDISP-2 is installed.  With the 61-7347-1 Blank Cover installed, operator
interface must either be via "Fireye Explorer" pc software, or by temporarily installing a 95DISP-1 or
95WIDISP-2.

The 95DSS3 InSight II flame scanner requires either the 95DISP-1 Display, the 95DISP-1-SS dis-
play, the 95WIDISP-2 Transmitter, or the 61-7347-1 Blank Cover.  Refer to bulletin CU-113 for
detailed description of the 95DSS3 scanner.

INSTALLATION INSTRUCTIONS

The following are the steps required to install the 95DISP-1 Display, 95WIDISP-2 Transmitter, or
61-7347-1 Blank Cover into a new 95DSS3 InSight II scanner.  If you are replacing a 95DSS3 scan-
ner's damaged unit, you must first remove power from the scanner and move it to a clean, dry, non-
hazardous area.

CU-116

OCTOBER 13, 2015

95DISP-1 DISPLAY,

95DISP-1-SS DISPLAY,

95WIDISP-2 IR TRANSMITTER

and 61-7347-1 BLANK COVER

For use with 95DSS3

1. Remove the threaded Locking 
Ring from the 95DSS3 
scanner.

2. Remove the plastic end cap.

95WIDISP-2

95DISP-1

61-7347-1

3. Verify that the scanner housing
o-ring is properly seated in the
95DSS3 scanner.