INSTRUCTION MANUAL FOR INSTALLATION, MAINTENANCE AND
USE Rev−12
PMKIE−DIMU−GB−12
12
GB
INDIRECT TILTING PANS, ELECTRIC TYPE
ˆPMKIE100˜ ˆPMKIE150˜ ˆPMKIE200˜ ˆPMKIE300˜ ˆPMKIE500˜
3.2.1
ELECTRICAL CONNECTIONS AND EQUIPOTENTIAL BONDING
Warning! :
The appliance is supplied to operate according to the power supply indicated on the
data plate.
−
As mentioned, the appliance must be connected to the power supply by way of a multiple pole main
isolating switch and protection device that must be proportioned to the power of the appliance (1 mA per
kW of rated power).
−
The earthing system must be efficient.
−
As this appliance is type Y equipment (delivery without power cable and plug), the cable and other
hardware needed to make the connection to the electrical power supply must be provided by the installer.
−
The power cable shall be of the kind described in the paragraph “Electrical specification" and shall be
resistant to oil (type
H05RN-F
o
H07RN-F
).
−
The power terminal board can be reached by removing the lower front panel (unloose the screws). The
cable fastener is on the lower right-hand side.
−
The cable must be fed in from beneath the clamp. The individual wires are then fastened to the
corresponding terminals of the terminal board. The earth wire must be longer than the other wires, so that
in the event of the cable being jerked or the clamp broken, the live wires will disconnect first. Lock the cord
fastener.
ATTENTION!
Cut the tension before to make the connection and/or maintenance .
−
The appliance must incorporate an equipotential system.
−
Connect the terminal on the lower right-hand side marked with the international symbol
a connector
with a nominal cross section <10 mm2. All the appliances installed and the earth system of the building
shall be connected like this.
3.2.2
CONNECTION TO WATERWORKS
−
Water inlet pressure must be between 50 and 300 kPa, otherwise install a pressure regulator on the line
before the appliance.
−
Install a cut-off valve for each supply on the line before the appliance.
−
Water connections are fitted in the lower part on the right-hand side of the appliance.
−
Make connections according to regulations currently in force.