4
SPECIFICATIONS & FEATURES
DIP SWITCH SETTINGS:
Each Annunciator needs to be assigned a unique, sequential
“Address”
. This is done with DIP Switches, which also
allow disabling of some buttons.
SW1-1
=
Address A0
\
SW1-2
=
Address A1
>
Address “A3” is always “off”.
SW1-3
=
Address A2
/
SW1-4
=
When “off”, the System Reset and Signal Silence slide-switches are always disabled, regardless of the
operation of the keyswitch.
The Annunciator “Address” (see the Manual for the Fire Alarm Control Panel being used), is set as ...
DIP Switch Positions
Annunciator “Address”
1
2
3
4
5
6
7
SW1-1 (A0)
on
off
on
off
on
off
on
SW1-2 (A1)
off
on
on
off
off
on
on
SW1-3 (A2)
off
off
off
on
on
on
on
SW1-4 (A3)
off
off
off
off
off
off
off
Annunciators on a common RS-485 connection must be numbered sequentially; i.e.: 1,2,3,4, and not randomly
such as 5,3,7 !! Note that not all Annunciator “Addresses” are valid for all Fire Alarm Control Panels. Refer
to the Fire Alarm Control Panel Manual for further information.
Enclosure:
A standard 4-gang Electrical Box is used.
Electrical Specs.:
Ž
19 to 31 VDC (filtered or full-wave-rectified)
Ž
Slide-Switch Controls, LED indicators, and Keyswitch to enable Controls.
Ž
Local Buzzer, Indicators (AC-On, Common Trouble, Signal Silence), and Controls (System Reset, Lamp Test, Buzzer
Silence, Signal Silence).
Ž
Annunciation of up to 8 Points.
Ž
Not Expandable.
Ž
Standby: 35 mA Max., All LED’s “On”: 90 mA Max.
Current Drain for Battery Calculations:
The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a time. Thus
the currents are ...
Normal Standby
=
35 mA
Maximum
=
90 mA
The
Normal Standby Current
is used for Battery Size Calculations (see the Fire Alarm Control Panel manual) and includes
the current drain for the Trouble Buzzer, Trouble LED, and one Alarm LED. The
Maximum Current
is used to calculate the wire
size (see the
Wiring Instruction
).