FIREWOLF FW-RA-LED Wiring & Installation Instructions Download Page 3

3

CONTROLS & DISPLAYS:

For precise definitions of Control & Display operation, refer to the manual for the Fire Alarm Control Panel that the Annunciator
is being connected to.

Controls

Displays

System Reset, Signal Silence,

AC On, Common Trouble, Signal Silence,

Buzzer Silence, Lamp Test.

8 Circuit Status LED’s.

WIRING INSTRUCTION:

The 

RS-485 Wiring

 to the FW-RA-LED Module is

recommended to be 

Twisted Shielded Pair

 as

shown in the diagram. The wire gauge may be;

22 AWG up to

2000 ft.

20 AWG up to

4000 ft.

18 AWG up to

8000 ft.

The RS-485 wiring from the Fire Alarm Control
Panel to the Annunciator(s) must be point-to-point
from the FA Panel to the first Annunciator, then the
next Annunciator, and so on. 

No star-wiring or T-

tapping is allowed.

 Each RAM-208 Annunciator

Module has a 

120 ohm End-of-Line Resistor

 on

its RS-485 Output terminals. This is removed on
all except the last wired Module.

The 24 VDC field wiring needs to be of an
appropriate gauge for the number of annunciators
and the total wiring run length. See the

Specifications

 section 

“Current Drain for Battery

Calculations”

, and calculate the 

Maximum

 current

for all Annunciators summed together ...

NOTE:

Accidentally connecting any of the 24
VDC wires to the RS-485 wiring could
result in damage to the Annunciator
and/or to the Fire Alarm Control Panel that it is connected to !!!

Maximum for

MAXIMUM  WIRING  RUN  TO  LAST ANNUNCIATOR

MAX.  LOOP

all Annunciators

RESISTANCE

18AWG

16AWG

14AWG

12AWG

Amperes

ft

m

ft

m

ft

m

ft

m

Ohms

0.30

470

143

750

229

1200

366

1900

579

6

0.60

235

71

375

114

600

183

850

259

3

0.90

156

47

250

76

400

122

570

174

2

1.20

118

36

185

56

300

91

425

129

1.5

1.50

94

29

150

46

240

73

343

105

1.2

1.70

78

24

125

38

200

61

285

87

1.0