background image

DATE

TIME

EVENT

ACTION REQUIRED

DATE

INITIALS

COMPLETED

SYSTEM MAINTENANCE

The following checks are recommended in accordance with national requirements. Make an entry

in the log book every time a test is performed. Example of routine testing is shown below:

1.

Daily Inspection

- Check the SUPPLY indicator is illuminated and inspect for any fault

indicators showing or sounder operating, and that any previous faults have been attended to.

2.

Weekly Test

– Perform a lamp test, ensure all indicators illuminate. Put the panel into WALK

TEST and operate a call point or detector to test the system, followed by panel reset. Each

week choose a different zone and call point or detector in rotation.

3

Quarterly Test

– Check all previous log book entries and verify that all remedial action has

been taken. Operate a call point or detector on each zone to test the fire alarm as in 2 above.

Return the panel to its normal state, then isolate the mains supply and perform an EVACUATE

to ensure that the battery is capable of supplying the alarm sounders.

4.

Annual Test

– As in 2 and 3 above but test all call points and detectors for correct operation.

Using the double pole isolator, verify that the terminals of the mains terminal block are secure

and that the wires are securely fixed in place.

5.

Every 2-3 years

– Have the smoke detectors checked or changed by a fire alarm engineer to

ensure correct operation and freedom from potential false alarms.

6.

Every 5 years

– replace the sealed lead acid battery.

LOG BOOK

This log book should be maintained by a responsible person who should ensure that every entry is

properly recorded. An ‘event’ should include fire alarms (real and false), faults, tests, temporary

disconnections or zone isolations and the dates of service engineers visits and the work carried out.

Name and Address 

Person responsible

Date

Person responsible

Date 

Person responsible

Date 

The system was installed by

and is maintained under contract by

until 

Tel number

who should be contacted if service is required.

Summary of Contents for FTEN1

Page 1: ...when a fault on the sounder wiring DISABLED occurs Illuminated if alarm lines are disabled DISABLED Yellow Illuminated when Zones and or alarm are disabled The specific zone or alarm fault led will a...

Page 2: ...EN54 4 1997 SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER 1 1 1 tec tec EN54 EN54 EN54 FIRE FIRE FIRE TYPICAL PANEL WIRING NO SPURS ALLOWED END OF LINE COMPONENT ON LAST DETECTOR Zone Ve RED Zone Ve B...

Page 3: ...rs and callpoints used are compatible with the panel and that only devices recommended by the supplier are used 7 The correct end of line component is used on the detection and alarm circuits includin...

Page 4: ...the common fault indicator Used to drive a remote fault indicator TYPICAL PANEL WIRING NO SPURS ALLOWED END OF LINE COMPONENT ON LAST DETECTOR Zone Ve RED Zone Ve BLACK EOL COMPONENT ON ANY UNUSED ZO...

Page 5: ...5 5 5 EN54 2 1997 EN54 2 1997 EN54 2 1997 EN54 4 1997 EN54 4 1997 EN54 4 1997 SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER 1 1 1 tec tec EN54 EN54 EN54 FIRE FIRE FIRE SYSTEM FAULT SYSTEM FAULT SYSTEM...

Page 6: ...SYSTEM FAULT SYSTEM FAULT SYSTEM FAULT EARTH FAULT EARTH FAULT EARTH FAULT SUPPLY SUPPLY SUPPLY ZONES ZONES ZONES 2 2 2 1 1 3 3 3 4 4 4 SUPPLY FAULT SUPPLY FAULT SUPPLY FAULT DISABLED DISABLED DISABLE...

Page 7: ...ENERAL FIRE FAULT DISABLE TEST FAULT DISABLE FAULT DISABLE TEST TEST FIRE FIRE FIRE SILENCE BUZZER SILENCE SILENCE BUZZER BUZZER SILENCE ALARMS SILENCE SILENCE ALARMS ALARMS EXIT EXIT EXIT EVACUATE EV...

Page 8: ...rmal state then isolate the mains supply and perform an EVACUATE to ensure that the battery is capable of supplying the alarm sounders 4 Annual Test As in 2 and 3 above but test all call points and de...

Page 9: ...DATE TIME EVENT ACTION REQUIRED DATE INITIALS COMPLETED DATE TIME EVENT ACTION REQUIRED DATE INITIALS COMPLETED...

Page 10: ...bout 3 seconds 5344 1 Reset Return the system to a normal condition after a fire or fault has occurred This should only be performed when the fire or fault has been identified and alarms have been sil...

Reviews: