background image

 

FirePro

®

 

Technical Manual

 

 

Keep  this  Technical  Manual  for  future  use.  This 

manual lapses when revised. The latest version 

is obtainable from FirePro Systems Ltd.  

 

 

 

 

 

 

 

 
 

 

 

 

Version 1, 01-07-2010 

 

 

 

 

 

FirePro

®

 

products are manufactured by FirePro Systems Ltd

 

Page 1 of 6 
 

 

 
 
 

FPC-1 FIRE DETECTION AND EXTINGUISHANT CONTROLLER 

 
 

Introduction 

 
The FPC-1 is a self-contained aerosol activation module. 

The FPC-1 includes a heat sensor that operates as a fixed-temperature or Rate-of-Rise 
and fixed-temperature detector, input for optional manual activation switch and/or linear 

heat detector, control circuitry, and activation of two FirePro Aerosol units. 

The unit reports via open collector alarm condition, trouble condition, and provides 
"watch-dog" pulses to indicate the unit is alive. 

The module is operated by its own supervised power source. 
The FPC-1 is not intended to replace fire detection and automatic extinguishing systems 

that are required according to relevant regulations. 

An open or disconnected aerosol generator will not interfere with the operation of the 
other aerosol. 

 

 

Figure 1 

FPC-1 Fire Detection and Extinguishant Controller 

 

Installation 

 

Only authorised people should install the FPC-1. Install the unit on the top surface of the 
protected space or near the top as high as possible. Install the aerosol container 

according to the manufacturer's specification. 

 
 

Warning 

 

Disconnect all power sources when installing the FPC-1 in protected spaces that 

have power sources. 

1. 

Remove the module's top cover. 

2. 

Secure the module to the top surface of the protected space (see Figure 2 on page 

2 for location of the openings for mounting screws). 
3. 

Connect the first aerosol extinguisher to the terminal marked "Match 1". Connect 

the second aerosol extinguisher, if required, to the terminal marked "Match 2". Short 

"Match 2" output if a second aerosol is not used. 

Reviews: