Page | 14
7.3
Reset Function
To reset the control panel, press and hold Mode Switch 1 until 2 beeps are heard. Following
a reset, the control panel will automatically isolate. To restore the control panel to normal
operation, press Mode Switch 1
and ensure the “Isolated” LED turns off.
Note:
The control
panel
cannot
be reset if the activation sequence has been initiated. When the “Discharging”
LED is no longer illuminated, the reset function will become available again.
7.4
Test Function
The control panel includes a test function, enabling the operator to ensure that the control
panel is functioning correctly. To operate the test function, press and hold Mode Switch 1 until
3 beeps are heard. The test function will illuminate all LEDS on the control panel and operate
the internal sounder and any external siren/strobes for 2 seconds, and then return the control
panel to normal operation. The test function does not activate the suppression system.
Note:
If any LEDS or siren/strobes do not operate, contact your supplier.
7.5
Discharging the Fire System
To manually discharge the fire system, press and hold both Mode Switch 1 and Mode Switch
2 continuously for 5 seconds. This will immediately operate any installed siren/strobes and
any shutdown relays, to warn any occupants. Manually discharging the fire system should only
performed during commissioning/servicing when the system has been appropriately isolated,
or in case of fire.
7.6
Alarm Silence
To silence the internal sounder and any installed siren/strobes that have operated due to an
alarm condition, press and hold Mode Switch 1 until a 1 beep is heard and the “Isolated” LED
is illuminated. This will also override any installed shutdown relays and allow for operation of
the equipment.
Note:
Equipment should not be operated until it has been rendered safe by
the appropriate authority. The control panel will remain in an alarm/fault condition until
serviced and reset.