background image

 
 

 
 

                   

 

                                                                                Page 10 of 10 

 
 

 

MODEL K5 (w/Air Pump) BURNER COMPONENTS IDENTIFICATION 

 

(Actual parts may look different as Firelake often updates components to latest technologies) 

 

 

AIR FILTER           AIR PRESSURE SWITCH           OIL PRESSURE GAUGE&REGULATOR 
 

           OIL FEED PIPE                              IGNITER       SAFETY 

 

 

 
AIR PUMP OUTLET  

 

AIR PRESSURE ADJUSTING VALVE 

AIR GAUGE 

COMBUSTION AIR INLET PORTS   

 

NOT SHOWN IN ABOVE VIEW, THIS BURNER ALSO HAS A PRIMING TOGGLE SWITCH, 
SAFETY RESET BUTTON, FLAME RETENTION HEAD, AIR CONTROL BOX, & 
INDICATOR LIGHTS LIKE MODEL B5 BURNER (no Air Pump) PICTURE SHOWS. 

 
 
 
 

 

Summary of Contents for 155

Page 1: ...ust Be In Accordance With State and Local Codes and it is the responsibility of the installer to assure all codes are met Date Installed WARRANTY NOTICE Use of equipment on any equipment not manufactured or designed for use VOIDS the warranty property or personal damage could occur For service call your dealer or installer at ...

Page 2: ...UPPLY 17 OIL PUMP MOUNTING 17 FINISHING THE PLUMBING 17 ELECTRICAL CONNECTIONS 20 INITIAL START UP AND OPERATING SEQUENCE 33 FAN LIMIT SWITCH SETTINGS 35 FINE TUNING THE BURNER 36 PRIMARY CONTROL FUNCTION SAFETY LOCKOUT 37 ROUTINE HEATER AND BURNER MAINTENANCE 38 WEEKLY MAINTENANCE 38 BURNER 38 ASSEMBLY OF NOZZLE 39 ASSEMBLY OF OIL AND AIR SOLENOID 57190 40 ASSEMBLY OF OIL REGULATOR 57129 41 END O...

Page 3: ...cm 167 76kg 15 sq 38cm 245 82 2 1m 26 66cm 22 56cm 200 91kg 18 sq 46cm 315 96 2 5m 26 66cm 22 56cm 256 116kg 18 sq 46cm 235 42 1 1m 32 0 8m 33 84cm 350 160kg 23x29 58x74cm 350 55 1 4m 52 1 32m 33 84cm 800 364kg 23x29 58x74cm 500 55 1 4m 52 1 32m 33 84cm 800 364kg 23x41 58x104cm Overall Dimensions of Heater with Burner and Blower Model Length Width Height Weight 155 79 5 2 0m 22 56m 34 5 88cm 234 1...

Page 4: ...llation of equipment in the United States must consider the requirements of the following publications of the National Fire Protection Association Battery March Park Qunicy Massachusetts 02269 N F P A No 30 Flammable and Combustible Liquid Codes N F P A No 31 Standard for Installation of Oil Burning Equipment N F P A No 88A Standard for Parking Structures N F P A No 88B Standard for Repair Garages...

Page 5: ...Save box Accessory Carton Cleanable Oil Filter 1 2 Cutoff valve 3 4 Suction Screen 3 4 Check Valve Wall Thermostat 1 2 x 1 4 Swivel 3 4 x 1 2 Swivel 1 4 x 1 4 x 1 8 Tee 1 4 x 1 Hex Nipple 1 2 x 2 Hex Nipple 1 4 x 2 Nipple Warranty Card Manual 2 Pressure Gauge Barometric Damper for chimney Oil Transfer Pump COMPONENT IDENTIFICATION Crated or Boxed Exchanger Burner appearance varies by model Cleanou...

Page 6: ...on Cleanable Oil Filter Fan Motor 1 2 Cutoff valve 3 4 Suction Screen 3 4 Check Valve Wall Thermostat 1 2 x 1 4 Swivel 3 4 x 1 2 Swivel 1 4 x 1 4 x 1 8 Tee 1 4 x 1 Hex Nipple 1 2 x 2 Hex Nipple 1 4 x 2 Nipple Warranty Card Manual 2 Pressure Gauge Barometric Damper for chimney Oil Transfer Pump Fan Heat Exchanger w Cabinet Remove this cabinet panel to slide out fan accessories carton damper and acc...

Page 7: ...TE SIDE BAROMETRIC DAMPER STACK BURNER DOOR SIDE PANEL BASE DOOR GASKET VIEW PORT BURNER 2 Bolt on brackets each end for attaching to framework or rods Can be put on lower edge too BLOWER GUARD FAN SWITCH 6 X 6 ELECTRICAL BOX CORD LOCKING CLAMP BEHIND BRACKET PREVENTS BURNER DOOR FROM OPENING WHILE POWERED TAKE SLACK FROM CORD WHEN INSTALLING ...

Page 8: ...ATION LOUVERS HOT AIR OUTLET LOUVERS ARE NOT USED WITH DUCTED MODELS FAN CONTROL OFTEN CALLED FAN LIMIT SWITCH ELECTRICAL AND FAN RELAY JUNCTION BOXES VIEW PORT HINGED BURNER MOUNT CLEANING ACCESS PANEL FAN OPENING STACK COLLAR EXCHANGER CLEANING ACCESS PANEL ...

Page 9: ...earance from wire guard to blades Fan will flex toward motor when running Secure blade to shaft snugly using set screws Mark shaft to show hub s position Align motor s conduit to reach electrical box Align guard fan assembly to pilot holes on rear cabinet panel attach with screws Fan blades must not contact heater parts when turning After one day check the shaft mark regarding hub s position If it...

Page 10: ...AIR FILTER AIR PRESSURE SWITCH OIL PRESSURE GAUGE REGULATOR OIL FEED PIPE IGNITER SAFETY AIR PUMP OUTLET AIR PRESSURE ADJUSTING VALVE AIR GAUGE COMBUSTION AIR INLET PORTS NOT SHOWN IN ABOVE VIEW THIS BURNER ALSO HAS A PRIMING TOGGLE SWITCH SAFETY RESET BUTTON FLAME RETENTION HEAD AIR CONTROL BOX INDICATOR LIGHTS LIKE MODEL B5 BURNER no Air Pump PICTURE SHOWS ...

Page 11: ...logies IGNITION CONTROL PRIMARY CONTROL FLAME RETENTION HEAD OIL REGULATOR W OIL CONNECTION COMBUSTION AIR INLET BANDS IGNITOR TRANSFORMER BURNER MOUNT FLANGE RESET BUTTON PRIMING SWITCH OIL NOZZLE PRESSURE SLIDE GUN ASSEMBLY COMPRESSED AIR AIR CONTROL BOX SUPPLY CONNECTION INDICATOR LIGHTS 3 AIR NOZZLE PRESSURE AIR REGULATOR COMPRESSED AIR ...

Page 12: ...ning on the top of the heater so that the top of the air deflector is pinched between the blower housing and edge of the cabinet opening The blower is placed so that the flat blower housing side is facing the burner The blower is then secured to the top of the heater with 4 cap screws through the weld nuts in the cabinet 3 The fan limit switch attached to the 6 x 6 inch electrical box is factory l...

Page 13: ...Do not over tighten or insulation on electrodes may crack Examine electrode position after tightening to be sure position has not changed Replace hole plug 3 The electrodes should not touch surrounding metal parts or be too close together as they will restrict or divert the arc and not light the oil spray 4 Position the large white insulation gasket s found in the blower carton between the furnace...

Page 14: ...N PROPER DRAFT FOR EFFICIENT BURNING ASSURE THAT ADEQUATE MAKE UP AIR IS AVAILABLE NEGATIVE DRAFT REQUIREMENT 04 TO 06 INCHES OF WATER COLUMN AT FURNACE OUTLET BUILDING EXHAUST FANS OR COLD BUILDINGS AT NIGHT CAN REVERSE YOUR DRAFT AND CAUSE FUMES POOR COMBUSTION OR NUISANCE BURNER LOCKOUTS TAKE MEASURES TO ASSURE FURNACE WILL HAVE PROPER DRAFT DIRECTION WHEN OPERATING 5 If permanent masonry chimn...

Page 15: ...normal Starving the burner of air is more likely in smaller and well insulated weather tight rooms In poor natural draft conditions a draft inducer placed near the outlet can be used to improve poor draft conditions and should be placed as near the roof as possible Inducers will pull air better than push it A 1 4 HP like Grainger 4C732 or is suggested Smaller HP inducers and squirrel cage types wi...

Page 16: ... vent Locate inducer as close to where chimney exits building as practical Never allow rain or condensation to flow back into heater Taper end of stack to keep rain out Place a screen 1 2 or 3 4 openings over stack to keep animals out Extend stack away from building 18 or beyond gutters and eves Observe clearance to combustible materials ...

Page 17: ... water is present take all measures to remove it The air solenoid may stick and other components may rust and fail 3 SERVICE TIP 80 of service problems can be avoided by keeping contaminants like rust chips water pipe dope insects from reaching burner through the air and oil lines OIL PUMP MOUNTING 1 Consult your dealer for best plumbing methods before starting Mount the pump as near the oil suppl...

Page 18: ...fittings are acceptable never use compression fittings Meeting building codes and your needs may require deviation from the fittings provided in your accessory carton and described in the example below Components shown are provided with standard heater purchases and found in Accessory Carton With new J1000 pumps 1 4x1 8 1 2x1 4 bushings provided for use in pump ports 3 4 FPT Filter Gauges 3 4x1 2 ...

Page 19: ...ompression soft copper tubing is commonly used Hard metal tubing or metal pipe is acceptable but may incur more cost has more potential for leaks and is not flexible to swing the burner open for routine cleaning Consult your dealer on sizing for your application Try to run the oil piping uphill from the pump to the burner to allow entrapped air to escape at the burner Avoid high spots in the oil p...

Page 20: ...Wiring Main power feed from panel Hot Neutral Ground Prewired Blower Hot Neutral Oil Pump Hot Neutral hot is opposite red burner wire Prewired Fan Limit Black Blue and Red Prewired Burner Cord blue feeds black burner red feeds blower 1 Connect burner power cord coming from junction box to mating connection on burner Do note force internal moldings they permit only one orientation of connection Tig...

Page 21: ...Page 21 of 21 APPLIES TO ALL HEATER MODELS EXCEPT MODEL 500 ...

Page 22: ...wer Relay Burner Cord Oil Pump Hot to RED Burner wire Pump Neutral to any WHITE Picture is for reference see following wiring diagrams COMPLETING WIRING 3 Connect burner power cord coming from junction box to mating connection on burner Do note force Internal moldings permit only one orientation of connection Tighten locking ring to secure Run cord through clamp located on top of cabinet remove sl...

Page 23: ...Page 23 of 23 MODEL 500 HEATER ONLY 220 VAC FEED ...

Page 24: ...which burner you have Three models are made K5 B5 B5 Two Stage The easiest way to determine is Does the burner have an Air Pump Filter attached at the side of the housing YES NO then it is a K5 model burner then it is a B5 model burner Use K5 identified diagrams Two B5 models are made See below The most common is the standard B5 shown here The other burner is a B5 Two Stage It has a Solenoid piped...

Page 25: ...e popped up before twisting knob push back down after adjusting 7 The preheated oil and air are mixed at the nozzle and the fuel is atomized as the electrodes arc for ignition The red light will cycle on off to automatically to preheat oil in block 8 Observe flame A proper flame in Model 155 200 245 315 will extend 1 4 to 1 3 the way down chamber approximately under where the blower is mounted Thr...

Page 26: ...d the fan limit switch closes thus starting the blower to push heated air into the room 11 When the room thermostat is satisfied the power to the ignition system will be interrupted thus causing the burner to shut down The blower will continue to operate until the heat exchanger temperature reduces to 90 F at the fan limit switch ...

Page 27: ...Page 27 of 27 K5 Burner w Air Pump 1 of 2 Burner Drawing ...

Page 28: ...Page 28 of 28 K5 Burner w Air Pump 2 of 2 Burner Drawing ...

Page 29: ...Page 29 of 29 B5 Burner Drawing ...

Page 30: ...Page 30 of 30 B5 Burner Drawing ...

Page 31: ...er relay The oil solenoid 300 Watt heater and green light receive power through the second timer relay Once the burner motor starts it has three seconds to close its centrifugal switch to establish power to the oil solenoid 300 Watt heater and green light If the centrifugal switch fails to close the oil solenoid 300 Watt heater and green light will lose power after six seconds when the second time...

Page 32: ... is mounted Three pass heater designs Model 235 350 500 will have flame approaching the target wall Excessive flame in any heater will damage metal burn poorly and void warranty If an adjustment is needed take a portable phone to the heater call your equipment dealer and explain the situation They will assist you to set oil or air flow for proper flame On non metering pump heaters to adjust flame ...

Page 33: ...Page 33 of 33 120 VOLT MODEL B5 TWO STAGE w AIR DELAY BURNER WIRING ...

Page 34: ...Page 34 of 34 HAS EXTRA AIR SOLENOID AND TIMERS 120 VOLT MODEL B5 TWO STAGE w AIR DELAY BURNER WIRING ...

Page 35: ... the fan limit switch will open and cut power to the blower motor 3 If there is a malfunction and the heated air reaches 200 F the control will cut the burner s power amber light goes out but the blower will continue to run trying to cool the exchanger This is a problem that needs corrected It may be due to excessive restriction of heated air from the heater a failed blower motor obstructed blower...

Page 36: ...e oil flow Metering Pumps are factory set no adjusting is available 3 Combustion air is admitted through the adjustable air bands on the side of the burner On models over 200 000 btu start with air band closed and face pointer at 10 On models under 200 000 btu start with air band closed and 5 for the face pointer Add just enough air to allow clean combustion Excess secondary air will reduce effici...

Page 37: ...ame for many seconds A signal measured in ohms is communicated between the cad cell and the primary control A poor or absent flame produces a high ohm reading When this signal is 1500 ohms the control may go into reset A signal indicating a very good flame is 500 ohms A moderate flame would be 500 to 1000 ohms 2 The cad cell has failed lens is dirty or retention head is dirty 3 The retention head ...

Page 38: ...e door gasket Use cleaning rod with hoe brush end to move ash to ends of exchanger Scoop or vacuum ash from exchanger Remove stack sections as needed to get ash from inside of chimney Horizontal runs will collect ash and create draft problems if not cleaned regularly CAUTION Used oil may contain heavy metal compounds and foreign materials When burned the compounds are deposited in the furnace and ...

Page 39: ...s the electrical as it is withdrawn from air box housing Secure slide gun in vise by capturing the aluminum block 5 Remove nozzle and disassemble into three pieces Clean with solvents and soft cloth If wear is evident install a new nozzle Wear may be from burn marks from igniter arcing or abrasion by oil flow that enlarges the orifices 6 Inspect o ring replace if worn torn or deformed ASSEMBLY OF ...

Page 40: ...ance BLOCK 57181 O RING 57184 ORING 57182 PLATE 57177 ADAPTER 57179 SCREW 4 57181 ASSEMBLY OF OIL AND AIR SOLENOID 57190 BASE O RING 57194 ZINC PLUNGER W SPRING ASM 57192 NICKEL PLUNGER W SPRING ASM 57139 STEM W WRENCH FLATS SNAP RING COIL Pay attention to detail the solenoid base has a specific inlet and outlet direction ...

Page 41: ...NGER W SPRING ASM 57139 ORIFICE HOLES NOTE TWO IN BASE STEM W WRENCH FLATS SNAP RING COIL Pay attention to detail the solenoid base has a specific inlet and outlet direction ASSEMBLY OF OIL REGULATOR 57129 BASE VALVE SPRING VALVE GASKET 57111 FLOW SEAT 57128 57127 DIAPHRAGM SLIP RING REGULATING SPRING DISC BONNET ADJ SCREW ...

Page 42: ...ways Consult your dealer if you think this operation is needed on your burner ALUMINUM PREHEAT BLOCK NOZZLE END NOZZLE ADAPTER RECESS CAP SCREW TAP HOLES 4 AIR PORT OIL NOZZLE PORT OIL BOX END OIL PASSAGE TO FRONT OF BLOCK 160 DEGREE STAT TAP RETURN OIL PASSAGE FROM FRONT OF BLOCK 140 DEGREE STAT TAP OIL PASSAGE TO FRONT OF BLOCK 300 WATT HEATER PORT 130 WATT HEATER PORT OIL BOX END OIL FROM SOLEN...

Page 43: ...le electrodes head and other burner parts Replace any worn parts as needed Replace burner on heater so it will be ready for next season Some users flush burner with 2 fuel oil or kerosene before shutting it off for the season 5 Service oil tank screens and filters and screen in head of pump Pump gaskets are fragile so have a spare gasket available 6 Flush oil pump with 2 fuel oil or kerosene Reass...

Page 44: ...ceiving power and creating voltage for a arc Electrode tips should be free of carbon and ash buildup Tips should diverge to fan the arc over the nozzle 6 Check air pressure and volume in supply line Starting pressure should be be about 13 PSI but not fluctuate wildly or drift up and down A falling air pressure or inability to adjust to higher pressure can indicate inadequate volume of air supply 7...

Page 45: ...lowing the reset button to pop too easily 6 Exhaust fan in building reverses draft in chimney or cold building at night creates down draft The flame smokes on startup due to lack of proper draft and trips reset Smoke On Ignition 1 Oil flow too great adjust flow downward 2 Air pressure too low set approximately 13 psi and adjust as needed 3 Down draft or improper draft adjustments check barometric ...

Page 46: ...Page 46 of 46 Trouble Shooting Fan Control NOTE JUMPERS STAY IN PLACE BLACK BLUE RED WIRE RED BLACK BLUE WIRE Wires should be in proper location secure and probe dial free to turn ...

Page 47: ...AB L or R Side C 11430 CAB Stack End Mdl 155 D 100501 CAB Stack Outlet Cover Donut E 11437 CAB Blank Filler Panel for 155 F 102309 CAB Louvers 4 Panel Kit for 155 G 11242 CAB Base for 155 102358 Louver w bolts for 155 Each H 102359 Stack Cap 11230 AIR DEFLECTOR U SHAPE 56803 PAINT SPRAY 12OZ BLUE REFLEX I 56419 SWITCH FAN 5 IN UOF ...

Page 48: ...Motor Capacitor 15 UFD R 102200 Mounting Brackets Each 155 200 2 needed S 102365 Burner Door w internal Viewtube T No longer available 11932 Cab Painted Skin for Burner Door 11124 Handle for Viewport Door Screw knob U 102153 Door Gasket Each 1 16th inch 2 required V 11241 Air Divider for 155 Inside Cabinet 101223 Cleaning Rod for Hoe Blade 6 102362 Hoe for Cleaning Rod 101277 DECAL Horizon 102154 ...

Page 49: ... C 11430 CAB Stack End Mdl 200 D 100501 CAB Stack Outlet Cover Donut E 11437 CAB Blank Filler Panel for 200 F 12309 CAB Louver Panel Kit for 200 G 11442 CAB Base for 200 102358 Louver w bolts for 200 Each H 102359 Stack Cap for all 11457 AIR DEFLECTOR U SHAPE 56803 PAINT SPRAY 12OZ BLUE REFLEX I 56419 SWITCH FAN 5 IN UOF ...

Page 50: ... for capacitor Q 11431 CAB Burner End for 200 R 102200 Mounting Brackets Each 155 200 2 required S 102365 Burner Door All w internal Viewtube T No longer available 11932 Cab Painted Skin for Burner Door 11124 Handle for Viewport Screw Knob U 102153 Door Gasket Each 1 16th inch 2 required V 11456 Air Divider for 200 Inside Cabinet 2 reqd 101224 Clean Rod 5 ft w o Hoe Blade 102362 Hoe for Cleaning R...

Page 51: ...L or R Side C 11930 CAB Stack End Mdl 245 D 102353 CAB Stack Opening Cover E 11937 CAB Blank Filler Panel for 245 F 100837 CAB Louver Panel Kit for 245 G 11742 CAB Base for 245 56736 Louver wbolts for 245 H 102359 Stack Cap for all less insul 102154 Insulation for inside Stack Cap 100506 AIR DEFLECTOR U SHAPE ...

Page 52: ...101300 1 H P Motor Only for Blower Q 11931 CAB Burner End for 245 R 100200 Mounting Brackets Each 245 2 required S 102365 Burner Door all w internal Viewtube T OBSOLETE 11932 Painted Skin for Burner Door 11124 Handle for Viewport Door Screw knob U 102153 Door Gasket Each 1 16th inch 2 required V 11741 Air Divider for 245 Inside Cabinet 2 reqd 101223 Cleaning Rod for Hoe Blade 6 102362 Hoe for Clea...

Page 53: ...B 11939 CAB Mdl 315 L or R Side C 11930 CAB Stack End Mdl 315 D 102353 CAB Stack Outlet Cover Donut E 11937 CAB Blank Filler Panel for 315 F 100837 CAB Louver Panel Kit for 315 G 11942 CAB Base for 315 56736 LOUVER W BOLTS REQS 5 PER HTR H 102359 Stack Cap 56803 PAINT SPRAY 12OZ BLUE REFLEX ...

Page 54: ...KET 101300 1 H P Motor Only for Blower Q 11931 CAB Burner End for 315 R 100200 Mounting Brackets Each 315 2 required S 102365 Burner Door all w internal Viewtube T 100506 AIR DEFLECTOR U SHAPE 11932 Painted Skin for Burner Door 11124 Handle for Viewport Door Screw Knob U 102153 Door Gasket Each 1 16th inch 2 required V 100505 Air Divider for 315 Inside Cabinet 2 reqd 101223 Cleaning Rod for Hoe Bl...

Page 55: ...Page 55 of 55 BLUE CABINET MODEL 235 ...

Page 56: ...n Fan Guard 56433 Clamp Fan Guard w Screws 6 Clamps for Fan Guard with Screws set fo 6 J 56955 Junction Box WL60 UOF Junction Box 56958 CVR JCN Box Fan S W UOF Cover for Junction Box 57266 Strip Terminal 8 Pole 30 AMP 8 Pole Terminal Strip Heat Exchanger 56678 Heat EX CAB 235 L BRNR ACC Heat Exchanger Aluminized with Cabinet less Burner and Accessories 56669 Heat EX L CAB 235 L BRNR ACC Heat Excha...

Page 57: ...N LUGS B 56462 CAB BURNER SIDE 11170 CAB BASE SKIN C 8887 CAB DOOR PANEL D 6882 CAB FAN SIDE E 6846 LOUVER REQ 5 PER HEATER 6883 CAB LOUVER SIDE UPPER PANEL 6884 CAB LOUVER SIDE LOWER PANEL 100054 CAB VERT LOUVER PANEL BURNER SIDE 6885 CAB VERT LOUVER PANEL STACK SIDE 8782 8783 CAB VIEW BRNR HOLE COVER ORDER 1 EA ...

Page 58: ...CVR JCN BOX FAN UOF 57266 STRIP TERMINAL 8 POLE 30 AMP Heat Exchanger 56836 HEAT EX CAB 350 L BRNR ACC F 56420 SWITCH FAN 8 IN 55778 Tube 3 5od used Ht Exch HRPO 19 reqd K 57267 Sight Plate New Style 57270 Spring Handle for viewport L 57269 GLASS SIGHT 58869 Hinged Burner Mt w rod removable 57274 SMOKE OUTLET PL A W A 350 98 56966 REPAIR BAFFLE 96872 TARGET 350 500 Stainless Steel w bolts 56961 RE...

Page 59: ...ER SIDE A 8890 CAB TOP F500 STACK SIDE 11175 CAB BASE SKIN B 8886 CAB BURNER SIDE C 8887 CAB DOOR PANEL 100054 CAB VERT LOUVER PANEL BURNER SIDE 6885 CAB VERT LOUVER PANEL STACK SIDE 8726 CAB STACK SIDE 10 OPENING W HANDLE D 8888 CAB FAN SIDE 8782 8783 CAB VIEW BRNR HOLE COVER ORDER 1 EA ...

Page 60: ... 56432 GUARD FAN J 56955 Junction Box 6 x6 56958 CVR JCN BOX FAN UOF 57266 STRIP TERMINAL 8 POLE 30 AMP 56951 FAN RELAY BOX UOF500UL 56954 RELAY FAN DPST NO 6 SPADE Heat Exchanger 56856 HT EXCH W CAB L ACC L BURNER 86789 Tube Cover a w asm w mt plates K 57267 Sight Plate New Style 57270 Spring Handle for viewport L 57269 GLASS SIGHT 58869 Hinged Burner Mt w rod removable 57277 SMOKE OUTLET A W ASM...

Page 61: ...ON USE W 56409 57155 FILTER SS 100171 W GAUGE 57151 REPL FILTER ELEMENT W ORING FOR 100171 57153 ORING ONLY FOR ELEMENT IN 100171 57158 FILTER AIR IN LINE 1 4 NPT 15711 VALVE BALL 1 2 NPT X 1 2 NPT 57263 VALVE BALL 1 2FNPT X 3 8FLARE 56680 SWIVEL 1 2 MPT X 1 4 FPT UOF 56681 SWIVEL 3 4 MPT X 1 2 FPT UOF 56683 TEE BLACK 1 4 X 1 4 X 1 8 56685 NIPPLE HEX 1 4 NPT X 1 4 NPT 56686 NIPPLE HEX 1 2 NPT X 2 ...

Page 62: ...OU 55715 COUPLING F TRANS PUMP 56927 GASKET FLAT A PUMP COVER 57264 SCREEN FILTER STRAINER A PUMP 55892 ADAPTER STEEL 1 4FPTX1 8MPT J Pump 56934 PUMP MDL J FACE PUMP ONLY 57201 MOTOR BRNR 1 4 HP 1725 RPM 57261 COUPLING OIL TRANSFER PUMP 56923 GASKET FLAT J PUMP COVER 57265 SCREEN FILTER STRAINER J PUMP 55892 ADAPTER STEEL 1 4FPTX1 8MPT ...

Page 63: ...Page 63 of 63 BURNERS ...

Page 64: ... SCREW 57144 GAUGE AIR VACUUM 60 PSI 57197 SCREW HEX WSHR TEK UNSL 57198 BUSHING BRASS 1 8 F X 1 4 M 57127 DIAPHRAGM 101050 Thumb 10 24 x 1 2 screw 57128 SEAT OIL REGLTR FLOW REGULAR 57111 GASKET REGULATOR SEAT 57190 SOLENOID OIL AIR 115V 60HZ F 57175 P HEAT BLOCK W PLUG 57 ALUM 101084 PLUG SQUARE HEAD W VIBRASEAL 101261 INSERT BIT 7 16 X 3 16 ML SQ 57195 TUBE COPPER 1 4 OD UOB 57196 NIPPLE GALV 1...

Page 65: ...Page 65 of 65 BURNERS CONTINUED ...

Page 66: ... 2 BUSS BNR WOF TRNSFR L 57209 CELL CADMIUM 60 IN LEADS M 57205 AIR TUBE W FLANGE DRILLED UOF N 57116 RETENTION HEAD 45 DEG SS B5 O 57204 BLWR WHEEL UOB125M UOB500M P1 57200 MOTOR BRNR 1 7HP NOT FOR AIR PUMP 56974 AIR RESTRICTOR PLATE W BOLTS 10558530 1 2 Knock Out Seal for Burner Housing 52321 SHUTTER AIR F BURNER 56377 BAND AIR BECKETT BRNR 10850270 LABEL Hot 57280 GROMMET RBR5 8IDX1 1 8ODX5 16 ...

Page 67: ...Page 67 of 67 BURNERS CONTINUED ...

Page 68: ...HOUR W 2 LEADS 57215 BRKT HOBBS HR METER UOB 57235 QUICK DISCONNECT CORD MALE 57240 DISCONNECT ASM QUICK CORD FEM S 57207 CTRL ASM PRIMARY W BUTT SPLC 57190 SOLENOID OIL AIR 115V 60HZ 57194 O RING SOLENOID BOTTOM 57252 KIT CNVRT SNTEC COMBU AIR SOL 57169 TOGGLE SWITCH OIL PRIME 57180 AIR PROVING SWITCH UNIVERSAL 57174 AIR LINE ALUMINUM FOR NON AIR PUMP BRNR 57211 ELL 1 8 NPT X 1 4 COMP 57192 PLUNG...

Page 69: ...LUM BLWR MTR KIT UOF350D 3 4 HP 57450 DIRECT DRIVE 2 REQUIRED 115V 60HZ BLWR MTR KIT UOF350D 220 3 4H 57449 DIRECRT DRIVE 2 REQUIRED 220V 60HZ 57453 MOTOR BLWR 115V 60 3 4 3M300 57454 MOTOR BLWR 220V 60 3 4 3M222 57458 BLWR 3 4 HP 115 220 MTR 57459 WHEEL BLOWER B 3 4 HP 57451 STRAP FAN MTR CAPACITOR MT 38869 RELAY DPST 120V 56118 STRIP TERMINAL 6 POLE 20A WHT 57452 CAPACITOR 7 5 UF 370V 50 60 5642...

Page 70: ...ROUND OPNG B 54792 ADAPTER ANGLE 350 500 54791 CONNECTOR DUCT UOF D C 57400 FILTER AIR ALUM 55787 BLWR MTR UOF500D 1HP 220V 60H 55789 MOTOR BLWR 1HP 220V 60HZ 57405 BLWR 175D 235D 500D 2C975 38869 RELAY DPST 120V 56118 STRIP TERMINAL 6 POLE 20A WHT 43015600 BELT BLWR KIT 4L480 1 43015620 PULLEY BLOWER KT 5 8 43015610 PULLEY BLOWER KT ...

Page 71: ... of proper maintenance shall not be considered defects under the Warranty 5 Use of solvents or other highly flammable fluids such as but not limited to benzene methylethyl ketones toluene xylene or naptha with Used Oil Fired products shall void this Warranty 6 Modification of products by a distributor dealer or end user shall void this Warranty unless specifically authorized in writing by the Manu...

Page 72: ... suffer as a result of any defect in the product Consequential or special damages as used herein include but are not limited to lost or damaged products or goods costs of transportation lost sales lost orders lost income increased overhead labor and incidental costs and operational inefficiencies THIS WARRANTY CONSTITUTES THE MANUFACTURER S ENTIRE AND SOLE WARRANTY AND THIS MANUFACTURER EXPRESSLEY...

Reviews: