REV. A Page 6
Drop in Pan - AWS Fire Pits
PREPARING A NON-COMBUSTIBLE STRUCTURE
IMPORTANT
Installation of Natural or LP gas should be done by a
qualified installer, service agency or gas supplier.
This appliance must be isolated from the gas supply
piping system by closing its manual shutoff valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than ½” psi (3.5kPa)
VENTILATION FOR NON-COMBUSTIBLE
ENCLOSURE
Fire features are subjected to many outdoor elements
such as rain, snow, wind, heat or cold.
A minimum of 18
square inches (opposite sides) of cross ventilation is
required to keep the components in good working
order.
Use Fig. 4 on as guide to assist to incorporate
proper ventilation.
HIGH ELEVATION INSTALLATION
This appliance is listed for elevations from 0- 4500 feet in
Canada and the U.S. If elevation exceeds 4500 feet it may
be necessary to decrease the input rating by changing the
existing burner orifice to a smaller size. Input should be
reduced 4% for each 1000 feet beyond the 4500 feet
above sea level. Check with your local gas utility for
assistance in determining the proper orifice in your
location. In some cases the heating value may already be
reduced and downsizing the orifice may not be necessary.
HARD PIPING TO FIRE FEATURE WITHOUT GAS
PROXIMITY
NOTE:
Refer to the NFPA54 (National Fuel Gas Code) for
proper pipe sizing. See gas line sizing chart on page 7 as
a reference.
1. Turn
OFF
gas supply system.
NOTE
: All gas
connections (except for brass to brass) require the
following. Clean pipe threads using either a wire brush
or steel wool. Apply pipe sealant to the fittings before
making any connection.
2. Ensure all gas connections are snug, but do not over
tighten!
BE CAREFUL!
3. Install necessary pipe for the distance required and a
manual shut-off valve at the exterior house wall. Check
with local codes for proper procedures. If pipe is to
pass through a foundation or house wall, make sure
to seal the area around the pipe with weather sealant.
Consult a plumber for proper installation to ensure you
are providing adequate gas supply for your application.
4. The primary gas shut-off (not supplied) will require a ½”
male flared fitting to enable connection of the stainless
steel flex gas line (not supplied) with the fire feature
(see Fig. 5 page 9).
5. Do not place an LP tank inside any fire pit enclosure.
Locate all Liquid Propane (LP) tanks outside the
enclosure.
6. To prevent performance problems with LP gas fire pits,
do not use a LP tank less than 100lbs. capacity.
DESCRIPTION
This is a field serviceable (30VDC)
commercial grade outdoor electronic system with a
maximum gas capacity of 290,000 Btu’s and it is shipped
as Natural (NG) or Propane (LP) gas models. It must be
installed with a burner pan, burner, orifice and installed into
a non-combustible enclosure. The “All Weather System”
(AWS) requires a 120VAC Ground Fault Interrupter (GFI)
to be installed in a weatherproof box. The power supply
Model #GOE-30VDC is used for a single installation greater
than 10-feet or more from pools or spas.
In the absence of local codes use the latest edition of the
National Fuel Gas Code NFPA54 and National Electrical
Code (NEC), or NFPA 70. The weatherproof box (supplied)
should be mounted securely within 6-feet of the GFI box.
The GFI box can power the adapter and optional remote
control receiver, if applicable.
Note
: Gas line must be
bonded at EACH FIRE FEATURE. See NEC- 680.26B
READ THIS MANUAL COMPLETELY BEFORE
BEGINNING INSTALLATION. UNDERSTAND HOW THE
AWS SYSTEMS OPERATES AND INSTALLS.
Fig. 4
Shows cross ventilation for a linear enclosure.
LEVEL FLAT SURFACE
Install fire feature on any level,
outdoor non-combustible, flat stable surface or a
combustible floor according to the clearances specified in
this manual for a Firegear burner.
NOTE
: Depending on
venting locations, do not place fire pit directly on grass,
dirt, or rocks that could prevent proper ventilation.
Ensure
proper water drainage is also incorporated into the fire
feature enclosure.
Fire Pit
Enclousure
(2) 6”x12”
Vents
Examples of Cross Ventilation
2- Firegear 6 x12 vents
(Model # VENT-KIT-6X12)
Cross Flow Ventilation
(Min. 18 Sq. In. Per Side)