OGF - ZC Series

INSTALLATION REQUIREMENTS

DEFINITION

Installation of a Firefox OGF-ZC series open fronted steel firebox into a timber framed and 

plasterboard enclosure in conjunction with the specified steel flueing system to draw and 

exhaust combustion gases up and away from the gas log firegrate.

1. Ensure that any air extraction devices located in the vicinity of the fireplace will not cause a 

negative air pressure (suction) which could cause a spillage of combustion gases into the room 

where the firebox is located when in operation.

2. GAS SUPPLY REQUIREMENT:  Provide a 12mm (1/2”) copper gas pipe into the chamber with a 

tail approx. ¾ of the way into the firebox.  An access hole is provided on the right hand side of the 

unit 130mm up from the base and 140mm in from the front of the unit.  For MJ/HR rating of the gas 

firegrate burner refer to specification pages.

3. ELECTRICAL SUPPLY:  The firebox is supplied with 1.5m of lead and a 3 pin plug located on the 

lower left hand side of the unit.  The lead must not rise above 100mm of the base level of the firebox.  

If connecting to a wall mounted isolating switch, ensure that the switch is far enough away so as to 

not obstruct the fitting of a decorative surround i.e. mantelpiece.

4. Construct timber framing as required to suit the selected Firefox firebox (See example detail).

.  Maintain 25mm clearance to the sides and back of the firebox and 50mm clearance from the

   top from combustible materials.

.  Secure firebox into position with metal strapping.

.  Plasterboard can be zero clearance to the perimeter face flange of the unit.  

5. FLUEING REQUIREMENTS:  

. Use the specified Twin Skin Flue system i.e. stainless steel inner flue PLUS the galvanized steel        

  outer flue casing.

.  Secure inner stainless flues at each crimp joint with 4 pop rivets.

.  Secure outer galvanized casing at each crimp joint with 4 x 25mm self tapping screws.

.  A 25mm clearance to all combustible materials is required from the outer flue casing.

.  Fit approved cowl as specified for the selected firebox/flue.

6. Permanent ventilation equal to the cross sectional area of the specified firebox flue must be 

provided into the room/area the gas fire is located.

7. Use only the appropriate Firefox gas firegrate/burner (GFG) in conjunction with the selected 

Firefox OGF/ZC firebox 

See GFG (GAS FIREGRATE) Specifications located in the following pages.

For installation and commissioning procedure of the gas burner/firegrate (GFG) refer to separate 

details entitled:

 

INSTALLATION & OPERATING INSTRUCTIONS ‘GFG’ Series GAS FIREGRATES 

Summary of Contents for OGF - 2.7/ZC

Page 1: ...egulations AGA 601 code for installation of gas burning appliances electrical wiring regulations and any other statutory requirement The guidelines here in have been tested and approved to AS 4558 AG 108 AGAApproval No 6386 HOT AIR OUTLETS FLUE SPIGOT FIREFOX OGF ZC FIREBOX CONTROL COVER PANEL GAS INLET COLD AIR INTAKE FAN SWITCH ELECTRIC CORD GAS FIREGRATE GFG For the appropriate Gas Firegrate GF...

Page 2: ... to not obstruct the fitting of a decorative surround i e mantelpiece 4 Construct timber framing as required to suit the selected Firefox firebox See example detail Maintain 25mm clearance to the sides and back of the firebox and 50mm clearance from the top from combustible materials Secure firebox into position with metal strapping Plasterboard can be zero clearance to the perimeter face flange o...

Page 3: ...ED SURROUND CHECK SPEC SELECTION FRAME DEPTH 300 MIN INNER FLUE STAINLESS SEE BELOW 130 R L 25 NOTE DO NOT LOCATE ANY EXTRACTION AIR DEVICE WHICH MAY CAUSE A NEGATIVE AIR PRESSURE IN THE ROOM WHERE THE GAS FIRE IS LOCATED VENTILATION OF 400cm2 IS REQUIRED INTO THE ROOM WHERE THE GAS FIRE IS LOCATED e g ROOF CEILING SPACE OUTSIDE WALL CAVITY OR SUB FLR AREA PLUMBING ELECTRICAL MUST BE CARRIED OUT B...

Page 4: ...g procedure of the Gas Firegrate Burner GFG refer to seperate instructions entitled INSTALLATION OPERATING INSTRUCTIONS GFG Series FIREGRATES FIREBOX MODEL FIREBOX DIMENSIONS A B C D E F 720 655 400 160 680 630 780 690 420 155 740 665 900 725 435 155 860 700 FLUE INNER OUTER 178 7 229 9 203 8 254 10 229 9 280 11 APPROPRIATE GAS FIREGRATE GFG GFG 2 7 GAS INPUT NG LP 36 35 Mj Hr 41 40 Mj Hr 52 50 Mj...

Page 5: ...her than 50mm max forward of the face of the firebox Mantle shelves must be 300mm min clear above the top edge of the firebox and must not project more than 250mm max forward of the face of the firebox A non combustible floor protector forehearth at the base directly in front of the firebox opening must be a minimum of 6mm thick project a minimum 300mm forward and 200mm on each side of the firebox...

Page 6: ... area where the FIREFOX is located The fan control switch is located on the lower left hand front of the unit The fan can remain OFF whilist the gas firegate is in operation To boost heat output simply select one of the two fan speeds avaliable i e LOW or HIGH Your FIREFOX gas unit is relatively maintenance free However we recommend that you have the appliance installation checked once a year to e...

Reviews: