INSTALLATION REQUIREMENTS

DEFINITION

Installation of a Firefox OGF-RT series open fronted steel firebox into an existing fireplace chamber and 

chimney which must be completely constructed of masonry and otherwise suitable for solid fuel burning 

e.g. wood.

1. Check that the fireplace chamber and chimney is structurally sound.

2. Chimney dampers or baffles must be removed or permanently fixed open.  The chimney must be free of 

any obstructions which may cause a restriction in up-draught.  It is mandatory that the fireplace has 

sufficient up-draught in order to draw and exhaust combustion gases away and up the chimney.

3. Check that any air extraction devices located in the vicinity of the fireplace do not cause a 

negative air pressure (suction) which could cause a spillage of combustion gases into the room where the 

fireplace is located when in operation.

4. Permanent ventilation with a minimum cross sectional area of 40,000mm sq (64” sq) must be provided 

into the room/area where the gas fire is located.

5. The fireplace chamber must be wide and deep enough to fully accommodate the Firefox steel firebox. 

The masonry rollback at the rear of the existing fireplace chamber may be removed if extra depth is 

required. The exhaust outlet at the top of the Firefox gas firebox must be free of obstruction so combustion 

waste can exhaust freely up into the chimney and away.

6. GAS SUPPLY REQUIREMENT:  Provide a 12mm (1/2”) copper gas pipe into the chamber with a tail 

approx. ¾ of the way into the firebox.  An access hole is provided on the right hand side of the unit 130mm 

up from the base and 140mm in from the front of the unit.  For MJ/HR rating of the gas firegrate burner 

refer to specification pages.

7. ELECTRICAL SUPPLY:  The firebox is supplied with 1.5m of lead and a 3 pin plug located on the lower 

left hand side of the unit.  The lead must not rise above 100mm of the base level of the firebox.  If 

connecting to a wall mounted isolating switch, ensure that the switch is far enough away so as to not 

obstruct the fitting of a decorative surround i.e. mantelpiece.

8. Wrap the firebox with the insulation provided and slide the unit into the chamber.  The firebox must be 

completely sealed around the perimeter face of the existing fireplace opening.

9. Use only the appropriate Firefox gas firegrate/burner (GFG) in conjunction with the selected Firefox 

OGF/RT firebox 

See GFG Series (GAS FIREGRATE) specifications, located in the following pages.

10. A gas cowl with a minimum diameter of 225mm approved AGA must be fitted to the top of the chimney.

For installation and commissioning procedure of the gas burner/firegrate (GFG) refer to separate details 

entitled: INSTALLATION & OPERATING INSTRUCTIONS ‘GFG’ Series GAS FIREGRATES.