OGF - ME Series

OPEN GAS FIREBOX

INSTALLATION & OPERATING INSTRUCTIONS

MODELS: OGF - 2.7/ME

OGF - 3.0/ME

OGF - 3.5/ME

FIREFOX INDUSTRIES PTY LTD

ACN 074 490 654

Factory 4, 15 Stud Road Bayswater, Victoria 3153 AUSTRALIA  Ph: (03) 9720 9055 Fax: (03) 9720 9255

This appliance must be installed by 

authorized personnel in accordance with

manufacturers instructions, gas fitting

regulations, AGA 601 code for installation

of gas burning appliances, electrical wiring

regulations and any other statutory 

requirement. The guidelines here-in

have been tested and approved to

AS 4558/AG 108. AGA Approval No. 6386.

HOT AIR OUTLETS

FLUE SPIGOT

FIREFOX “OGF-ME”

FIREBOX

CONTROL COVER 

PANEL

GAS INLET

COLD AIR INTAKE

FAN SWITCH

ELECTRIC

CORD

GAS

FIREGRATE   ‘GFG’

For the appropriate Gas Firegrate ‘GFG’

to be used in conjunction with the Gas

Firebox (OGF). See specification pages

on the back of booklet.

GAS

ENT

RY

CONTROL

COVER PANEL

DECORATIVE FRONT IRON

Spec 20.1.11

FC

Summary of Contents for OGF - 2.7/ME

Page 1: ...tions AGA 601 code for installation of gas burning appliances electrical wiring regulations and any other statutory requirement The guidelines here in have been tested and approved to AS 4558 AG 108 AGAApproval No 6386 HOT AIR OUTLETS FLUE SPIGOT FIREFOX OGF ME FIREBOX CONTROL COVER PANEL GAS INLET COLD AIR INTAKE FAN SWITCH ELECTRIC CORD GAS FIREGRATE GFG For the appropriate Gas Firegrate GFG to ...

Page 2: ...i e mantelpiece 4 Construct a non combustible enclosure as required to suit the selected Firefox OGF ME series gas firebox The enclosure must completely surround the base sides and back of the unit and rise 300mm above the top of the unit Plasterboard can be Zero Clearance to the perimeter face flange of the unit 5 FLUEING REQUIREMENTS Use the specified single skin galvanised inner active flue ONL...

Page 3: ...erating Instructions 25 NOTE DO NOT LOCATE ANY EXTRACTION AIR DEVICE WHICH MAY CAUSE A NEGATIVE AIR PRESSURE IN THE ROOM WHERE THE GAS FIRE IS LOCATED VENTILATION OF 400cm IS REQUIRED INTO THE ROOM WHERE THE GAS FIRE IS LOCATED e g ROOF CEILING SPACE OUTSIDE WALL CAVITY OR SUB FLR AREA PLUMBING ELECTRICAL MUST BE CARRIED OUT BY AN AUTHORISED PERSON 275 B OPTIONAL BRICK ENCLOSURE TO INNER SINGLE SK...

Page 4: ... 2 7 GFG 3 0 GFG 3 5 GAS INPUT 36 35 Mj Hr 41 40 Mj Hr 52 50 Mj Hr FIREBOX MODEL FIREBOX DIMENSIONS A B C D E F 720 640 370 160 620 605 780 640 390 155 680 605 900 640 405 155 800 605 178 7 229 9 203 8 254 10 229 9 280 11 APPROPRIATE GAS FIREGRATE GFG FLUE INNER OUTER For installation and commisioning procedure of the Gas Firegrate Burner GFG refer to seperate instructions entitled INSTALLATION OP...

Page 5: ...han 50mm max forward of the face of the firebox Mantle shelves must be 300mm min clear above the top edge of the firebox and must not project more than 250mm max forward of the face of the firebox A non combustible floor protector forehearth at the base directly in front of the firebox opening must be a minimum of 6mm thick project a minimum 300mm forward and 200mm on each side of the firebox open...

Page 6: ...area where the FIREFOX is located The fan control switch is located on the lower left hand front of the unit The fan can remain OFF whilist the gas firegate is in operation To boost heat output simply select one of the two fan speeds avaliable i e LOW or HIGH Your FIREFOX gas unit is relatively maintenance free However we recommend that you have the appliance installation checked once a year to en...

Reviews: