Firefox OGF - 2.7/ME Installation & Operating Instructions Manual Download Page 2

OGF - ME Series

INSTALLATION REQUIREMENTS

DEFINITION

Installation of a Firefox OGF-ME series open fronted steel firebox into a non-combustible enclosure 

constructed partially of masonry e.g. brick, concrete or Hebel blocks in conjunction with the specified 

steel flueing system to draw and exhaust combustion gases up and away from the gas log firegrate.

1. Ensure that any air extraction devices located in the vicinity of the fireplace will not cause a 

negative air pressure (suction) which could cause a spillage of combustion gases into the room where 

the firebox is located when in operation.

2. GAS SUPPLY REQUIREMENT:  Provide a 12mm (1/2”) copper gas pipe into the chamber with a 

tail approx. ¾ of the way into the firebox.  An access hole is provided on the right hand side of the unit 

130mm up from the base and 140mm in from the front of the unit.  For MJ/HR rating of the gas 

firegrate burner refer to specification pages.

3.  ELECTRICAL SUPPLY:  The firebox is supplied with 1.5m of lead and a 3 pin plug located on the 

lower left hand side of the unit.  The lead must not rise above 100mm of the base level of the firebox.  

If connecting to a wall mounted isolating switch, ensure that the switch is far enough away so as to not 

obstruct the fitting of a decorative surround i.e. mantelpiece.

4.  Construct a non-combustible enclosure as required to suit the selected Firefox OGF-ME series gas 

firebox.  The enclosure must completely surround the base, sides and back of the unit and rise 

300mm above the top of the unit.  Plasterboard can be Zero Clearance to the perimeter face flange of 

the unit.

5.  FLUEING REQUIREMENTS:

. Use the specified single skin galvanised inner active flue ONLY if the firebox and flue is to be 

completely enclosed in masonry.            

.  Use the specified twin skin flue system i.e. galvanised inner active flue  PLUS the galvanised  

outer casing if the flue is to be exposed close to combustible materials i.e. timber framing.

.  Secure inner active flues at each crimp joint with 4 pop rivets.

.  Secure outer casings at each crimp joint with 4 x 25mm self tapping screws.

.  A 25mm clearance to all combustible materials is required from the outer flue casing.

.  Fit approved cowl as specified for the selected firebox/flue.

6.  Permanent ventilation equal to the cross sectional area of the specified firebox flue must be 

provided into the room/area the gas fire is located.

7. Use only the appropriate Firefox gas firegrate/burner (GFG) in conjunction with the selected Firefox 

OGF/ME firebox 

See GFG Series (GAS FIREGRATE) specifications

,

located in the following pages.

For installation and commissioning procedure of the gas burner/firegrate (GFG) refer to separate 

details entitled: FIREFOX INSTALLATION & OPERATING INSTRUCTIONS ‘GFG’ Series GAS 

FIREGRATES. 

1

Summary of Contents for OGF - 2.7/ME

Page 1: ...tions AGA 601 code for installation of gas burning appliances electrical wiring regulations and any other statutory requirement The guidelines here in have been tested and approved to AS 4558 AG 108 AGAApproval No 6386 HOT AIR OUTLETS FLUE SPIGOT FIREFOX OGF ME FIREBOX CONTROL COVER PANEL GAS INLET COLD AIR INTAKE FAN SWITCH ELECTRIC CORD GAS FIREGRATE GFG For the appropriate Gas Firegrate GFG to ...

Page 2: ...i e mantelpiece 4 Construct a non combustible enclosure as required to suit the selected Firefox OGF ME series gas firebox The enclosure must completely surround the base sides and back of the unit and rise 300mm above the top of the unit Plasterboard can be Zero Clearance to the perimeter face flange of the unit 5 FLUEING REQUIREMENTS Use the specified single skin galvanised inner active flue ONL...

Page 3: ...erating Instructions 25 NOTE DO NOT LOCATE ANY EXTRACTION AIR DEVICE WHICH MAY CAUSE A NEGATIVE AIR PRESSURE IN THE ROOM WHERE THE GAS FIRE IS LOCATED VENTILATION OF 400cm IS REQUIRED INTO THE ROOM WHERE THE GAS FIRE IS LOCATED e g ROOF CEILING SPACE OUTSIDE WALL CAVITY OR SUB FLR AREA PLUMBING ELECTRICAL MUST BE CARRIED OUT BY AN AUTHORISED PERSON 275 B OPTIONAL BRICK ENCLOSURE TO INNER SINGLE SK...

Page 4: ... 2 7 GFG 3 0 GFG 3 5 GAS INPUT 36 35 Mj Hr 41 40 Mj Hr 52 50 Mj Hr FIREBOX MODEL FIREBOX DIMENSIONS A B C D E F 720 640 370 160 620 605 780 640 390 155 680 605 900 640 405 155 800 605 178 7 229 9 203 8 254 10 229 9 280 11 APPROPRIATE GAS FIREGRATE GFG FLUE INNER OUTER For installation and commisioning procedure of the Gas Firegrate Burner GFG refer to seperate instructions entitled INSTALLATION OP...

Page 5: ...han 50mm max forward of the face of the firebox Mantle shelves must be 300mm min clear above the top edge of the firebox and must not project more than 250mm max forward of the face of the firebox A non combustible floor protector forehearth at the base directly in front of the firebox opening must be a minimum of 6mm thick project a minimum 300mm forward and 200mm on each side of the firebox open...

Page 6: ...area where the FIREFOX is located The fan control switch is located on the lower left hand front of the unit The fan can remain OFF whilist the gas firegate is in operation To boost heat output simply select one of the two fan speeds avaliable i e LOW or HIGH Your FIREFOX gas unit is relatively maintenance free However we recommend that you have the appliance installation checked once a year to en...

Reviews: