Page 14
CYGHPG12-24-User-Manual-v1.6.indd
7.
The LED indicators next to the chosen AC input will illuminate to show
the presence of power.
8.
Switch on the unit’s input breaker.
2.4.3.3 Connecting by Hard Wiring Into The AC Input Bus Bar
1.
Before any power connections are made, ensure that Cygnus HPG is
in Mode 4: Off. See
"3.1.1 Description Of The Power Modes" on page
17
2.
Open the main door by unlocking the three locks located at its right
hand side using the provided 5 mm double barb key See
"Fig. 5 - 5 mm
Double Barb Key" on page 14
.
3.
The Bus Bar is located at the bottom left corner.
4.
Ensure that the wire used is suitable for the application.
5.
Pass the cables through the rubber flap in the door
6.
Connect to the lower row of connections using 6 mm ring terminals.
7.
Remove the 10 mm nuts.
8.
Attach ring terminals, referring to
"Fig. 6 - AC & Aux. Bus Bar
Connections, Input Selector Switch" on page 14
AC & Aux. Bus Bar Connections,
Input Selector Switch