Integrated Fire Protection System
C
Trim Options - Vacuum Sprinkler System
FM-060M-0-88A
1. Semi-flange and full-flanged configuration
When required by the user,
F
IRE
F
LEX
®
VACTEC
®
unit can
be provided in either a semi-flanged of full-flanged
configuration.
The semi-flanged option provides flanged fittings only on
the water inlet pipe (side needs to be specified at the time
of order) and on the system riser outlet. The drain
manifold is provided with a threaded end that also needs
to have its side specified (left or right). The rest of the
fittings are the same as usual with the main components
being provided in the standard flanged/grooved
configuration.
The full-flanged option is the same as above but goes a
step further with the main components being also provided
with a flanged/flanged configuration.
When provided, the face of the flanges will always be
located 6 inches (150mm) from the outside face of the
mounting base or cabinet surface.
Figure 1 - Semi-flanged configuration for vacuum
sprinkler system
(shown without system trim)
Field Connection
to Water Supply
(specify side)
Flanged fitting
outside cabinet
(when provided)
FM-061H-0-225A
Flanged fitting outside cabinet
(when provided)
Threaded end
Field Connection
to Open Drain
(specify side)