FireClass Fire detection system FireClass Panels
3 Menu Details
Service and Maintenance Doc. version 1
11
3
Menu Details
A typical Main Menu screen is shown in Fig. 10.
In this guide only the “engineering” menu options under the
Service and Configuration options are covered. If any menu
option is not described in this guide, the details of that
option are covered in the FireClass User guide.
The sections below detail the menu options.
3.1
View Status|Commis.
Overview
Use this
Commis. O/View
option for a quick status
overview of the commissioning facilities of the control
panel. You see the type of screen shown in Fig. 11.
Most of the items in the screen relate to the switches – for
details of the options 1-7, see 3.5.4 “Switches“ on
page 17. For details on the option 8: Dis .NonLED Ops see
3.4 “Disablements|Non-LED Outputs“ on page 13.
A “Y” indicates that the mode is enabled.
A “Y” against the “Test Equipment” item indicates that there
is an external test equipment connected to the control
panel. As an example, a PC running the FireClass Checker.
A “Y” against the “Commis. User” item indicates that the
logged on user has the Commissioning access level.
3.2
View/Print Data|Loop Info
Use this Loop Information option to derive details about the
various loop point counters and the status of various points.
This option is accessible only by the Engineer.
3.2.1
Loop Point Counters
Use this
Loop Point Counters
option to check that the
panel configuration matches the physical state of the loop,
and to see the number of points on the loop.
This option appears abbreviated to
Loop Point Ctrs
in
the menu.
After specifying the loop name, you see a “please wait”
message until the count is complete.
If no faults are found, the type of screen shown in Fig.12 is
displayed.
The conditions for “passed” are as follows:
The number of configured points equals the number of
detected points on the loop.
Detected points from left, right and both sides are equal.
If not all conditions are met, you see the type of screen
shown in Fig. 13.
Fig. 10: Main Menu
Fig. 11: Commis. O/View
Main Menu
FireClass
Wed, 17-Aug-11
16:37
High Street Office
1 - Accept Events
2 - View Status
3 - Disablements
4 - Time / Date
5 - Event Log
6 - View/Print Data
7 - Service
8 - Configuration
9 - Test Buzzer,
LEDs & Display
Alarm Count: 0021
General
Flt P 011
Back
Commis. Overview
FireClass
Thu, 18-Aug-11
13:27
High Street Office
Panel :01
1-SDevPoll:
2-Lp.Shtdn:
4-Rate of Rise :
5-Fast Fault : Y
6-Device PowerUp :
7-Noisy Device :
8-Dis.NonLED OPs :
Test Equipment :
Commis. User :
General
Flt P 011
Back
>>Panel
>>
Loop Versions
For a 2- loop panel version, you can make a
choice between the configured loops
A
and
B
.
For a 4- loop panel version, you can make a
choice between the configured loops
A
,
B
,
C
and
D
.
Fig. 12: Loop Point Counters, Loop
Loop Point Counters
FireClass
Tue, 30-Aug-11
14:51
High Street Office
Counter
Loop : A
P A S S E D
Configured : 010
General
Flt P 007
Back
Details
Scan