![FireClass FC-P-S Service And Maintenance Manual Download Page 12](http://html1.mh-extra.com/html/fireclass/fc-p-s/fc-p-s_service-and-maintenance-manual_2291321012.webp)
3.3 View/Print Data|Forced Points
FireClass Fire detection system FireClass Panels
12
Service and Maintenance Doc. version 1
As you can see, the problem in the screen example is a
missing device.
Details screen
Press the
Details
key (F2) to see the type of screen in
Press the
>>
key to see more point addresses.
The connection status of each point is indicated by the
following symbols:
OK: point connected, configured and identified
(applies to point 33 and points 60 to 64)
Point was configured but not connected or
identified (applies to point 21)
Point was not configured but connected (applies to
point 6)
Scan screen
Press the
Scan
key (F3) to see the type of screen shown in
Press the
>>
key to see more point addresses.
The points are shown which were detected from both sides
(Left/Right).
They are displayed as follows:
. Empty (not used)
OK: detected from both sides (applies to points 33
and 82)
Only detected from left side (applies to points 2and
20)
Only detected from right side (applies to points 60
to 63)
3.2.2
Loop Point Status
Use this option to print the statuses of all the points of
different loops that are configured. The screen is displayed
as shown in Fig 16.
3.3
View/Print Data|Forced
Points
Use this Forced Points option to view the number of loop
points that are in the forced state.
Fig. 13: View Loop Point Counters, Attention
Fig. 14: Details
Loop Point Counters
FireClass
Tue, 30-Aug-11
14:51
High Street Office
Counter
Loop : A
A T T E N T I O N
Configured : 010
Conf. & Ident: 009
General
Flt P 007
Back
Details
Scan
Loop Point Counters
FireClass
Tue, 30-Aug-11
14:51
High Street Office
Details
Loop : A
Point 0123456789
0 : ..........
10 : ..........
20 : ..........
30 : ...o......
40 : ..........
50 : ..........
60 : ooooo.....
70 : ..........
80 : ..........
General
Flt P 007
Back
>>
c
u
Fig. 15: Scan
Fig. 16: Loop Point -Print Status
Loop Point Counters
FireClass
Tue, 30-Aug-11
14:51
High Street Office
Left / Right Scan
Loop : A
Point 0123456789
0 : ..........
10 : ..........
20 : . ........
30 : ...*......
40 : ..........
50 : ..........
60 : r.........
70 : ..........
80 : ..*.......
General
Flt P 007
Back
>>
l
l
rrrr
Loop Point Status
FireClass
Tue, 30-Aug-11
14:51
High Street Office
PRINT ONLY
All loops
General
Flt P 007
Back