TECHNICAL SPECIFICATION

Type Identification Value:

145

System Compatibility:

Use only with FC Fire Alarm Controllers

Environment:

Indoor Application only

Operating Temperature:

-25 to +70

o

C

Storage Temperature:

-40 to +80

o

C

Operating Humidity:

Up to 95% non-condensing

Dimensions (HxWxD):

87 x 148 x 14 mm

Weight

100g

Mounting Requirements:

One FC backbox surface mount

Battery Requirements:

Standby Current:

0.505mA

Alarm Current:

4.5mA

Recommended Wire Size:

Min. 1.5 mm

2

Max. 2.5 mm

2

Maximum Wiring Resistance
Monitored Circuit:

10

W

Addressable Device Conditions:

– Normal
– Active
– Short Circuit wiring fault
– Open Circuit wiring fault
– Device Type Invalid
– Device No Response

Electromagnetic Compatibility

The FC410CIM complies with the following:

Ø

product family standard EN50130-4 in respect of Conducted Distur-
bances, Radiated Immunity, Electrostatic Discharge, Fast Transients
and Slow High Energy;

Ø

EN61000-6-3 for emissions.

INTRODUCTION

The FC410CIM FC Addressable Contact Input Module is designed to moni-
tor fire contacts such as extinguishing system control, ventilation control, fire
door control etc. The FC410CIM can be configured as:

Ø

Two spur circuits (Class B) monitoring multiple normally open contacts,
with short circuit giving a fault output.

Ø

Two spur circuits (Class B) monitoring single normally closed contacts,
with short circuit giving a fault output.

Ø

Two spur circuits (Class B) monitoring multiple normally open contacts,
with short circuit giving an alarm.

FEATURES

FC410CIM monitoring features include the following configurable items:

Ø

Identifies all monitored contacts and signals to the Fire Controller the sta-
tus of monitored contacts and wiring to the contacts.

Ø

Can monitor a single normally closed contact.

Ø

Can monitor two Class B spur circuits.
A monitored contact going to the active state, on either spur circuit, will cause
FC410CIM to report the Active State back to the FireClass controller.

An LED reports FC410CIM status to the user.

Ø

The LED lights when the contact monitored by the FC410CIM has swit-
ched to the active (off normal) state.

Ø

The LED when normally off, will pulse when the FC410CIM is polled by
the controller.

WIRING NOTES

The following notes apply:

1)

There are no user-required settings (such as switches or headers) on
FC410CIM.

2)

All wiring must conform to the applicable standards.

3)

All conductors to be free of earths.

4)

Fit the PCB to the FC470CV cover.

5)

Connect wiring to the monitored contact. For FC410CIM typical wiring
configurations see Figures 4 to 6.

6)

Verify the correct polarity of wiring before connecting the FC410CIM to
the addressable loop circuit

+

Refer to Fig.4.
1) If only one circuit is used, the other circuit must be terminated with
200/100 ohm resistors in parallel or a single 68 ohm EOL resistor.
2) FireClass Console configuration selection - Style C (normally closed).

+

Refer to Fig.5.
1) If only one circuit is used, the other circuit must be terminated with 200
ohm EOL resistor.
2) FireClass Console configuration selection - Style C (normally open).

+

Refer to Fig. 6
FireClass Console configuration selection - Style B (normally open).
If only one circuit is used, the other circuit must be terminated with 200 ohm
EOL resistor.

INSTALLATION TO FC470CV DOUBLE GANG COVER

1)

Assemble the FC410CIM to M520 Double Gang cover, using the four
screws and washers provided.

2)

Fit cover onto FC backbox.

ADDRESS SETTINGS

The FC410CIM has a default factory set address of 255, this must be set to
the loop address of the device using the FC490ST Loop Service Tool. The
FC410CIM may be programmed with the address prior to being installed by
using the internal programming port (see Fig.2) or after being installed by
using the programming port on the front cover (see Fig.3).

+

Note: once the address has been programmed, take note of the device
location and address number, to include on site drawings.

+

Note: this device use one address only on the loop.

CABLING

Cables are to be selected in accordance with the system design document
and the requirements of the applicable standard. Two pairs of connection ter-
minals (L+ and L-) are provided on the terminal block. These terminals are
used for connecting the module on to the addressable circuit. The maximum
section of the cable that can be connected at any one terminal is 2.5mm

2

. The

section is calculated based on the characteristics of the cable and the load.

ASSOCIATED EQUIPMENT

The module fits onto a standard dual-gang backbox.

ORDERING INFORMATION

FC410CIM:

Contact Input Module:

FC470CV:

Double-Gang cover

RECYCLING INFORMATION

Customers are recommended to dispose of their used equipments (panels,
detectors, sirens, and other devices) in an environmentally sound manner.
Potential methods include reuse of parts or whole products and recycling of
products, components, and/or materials.

WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
DIRECTIVE

In the European Union, this label indicates that this product
should NOT be disposed of with household waste. It should be
deposited at an appropriate facility to enable recovery and re-
cycling.

The manufacturer reserves the right to change the technical specifications
of this product without prior notice.

ENGLISH